Additional Short Circuit Current Ratings
Square D I-Line plug-on lugs installed in this I-Line Combo switchboard
and protected by indicated Square D circuit breakers are suitable for use
where the available short circuit current is not greater than that shown in
the following table. The short circuit current rating cannot exceed the
rating marked on the protecting circuit breaker. The protecting circuit
breakers may be the main or, if plugged onto the same I-Line bus stack,
may be downstream from the plug-on lugs.
Table 9: Short Circuit Current Ratings for Plug-On Lugs with
Protective Circuit Breakers
Catalog Number
and Ampere
Rating
Protecting Circuit Breakers
Maximum Available
Short Circuit Current
Catalog
Prefix
Number
of Poles
Maximum
Amperes
RMS Sym.
kA
Volts AC
SL100, 100 A
SL225, 225 A
SL250, 250 A
SL400, 400 A
SL800, 800 A
SL800M5, 800 A
SL1200P5, 1200 A
1
SL1200P6, 1200 A
1
SL1200P7, 1200 A
1
S33931, 1200 A
1
FA 2, 3 100
25 240
18 480
14 600
FH 2, 3 100
65 240
25 480
18 600
FD 2, 3 100
25 240
18 480Y
FG 2, 3 100
65 240
35 480Y
FJ 2, 3 100
100 240
65 480Y
SL225, 225 A
SL400, 400 A
SL800, 800 A
SL800M5, 800 A
SL1200P5, 1200 A
1
SL1200P6, 1200 A
1
SL1200P7, 1200 A
1
S33931, 1200 A
1
KA 2, 3 225
42 240
25 480
22 600
KH 2, 3 225
65 240
35 480
25 600
KC 2, 3 225
100 240
65 480
KI 2, 3 225
200 240
200 480
100 600
SL400, 400 A
SL800, 800 A
SL800M5, 800 A
SL1200P5, 1200 A
1
SL1200P6, 1200 A
1
SL1200P7, 1200 A
1
S33931, 1200 A
1
DG 3 400
65 240
35 480
DJ 3 400
100 240
65 480
DL 3 400
125 240
100 480
80043-808-01.book Page 51 Wednesday, March 22, 2017 12:31 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Square D I-Line and is the answer not in the manual?

Square D I-Line Specifications

General IconGeneral
Bus MaterialAluminum or Copper
Voltage Rating600V AC
Current RatingUp to 1200A
EnclosureNEMA 1
Poles2, 3
Interrupting Rating200 kA (depending on the specific model and installed breakers)