EasyManuals Logo

Square D I-Line User Manual

Default Icon
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
© 2013–2017 Schneider Electric All Rights Reserved
I-Line™ Combo Switchboards 80043-808-02 Rev. 02
Appendix 1: Specifications—Additional Short Circuit Current Ratings 03/2017
52
ENGLISH
SL800, 800 A
SL800M5, 800 A
SL1200P5, 1200 A
1
SL1200P6, 1200 A
1
SL1200P7, 1200 A
1
S33931, 1200 A
1
DG 3 600
65 240
35 480
DJ 3 600
100 240
65 480
DL 3 600
125 240
100 480
SL225, 225 A
SL250, 250 A
SL400, 400 A
SL800, 800 A
SL800M5, 800 A
SL1200, 1200 A
SL1200P5, 1200 A
SL1200P6, 1200 A
SL1200P7, 1200 A
S33930, 1200 A
S33931, 1200 A
BD6 2, 3 125
25 240
18 480
14 600Y
BG6 2, 3 125
65 240
35 480
18 600Y
BJ 2, 3 125
100 240
65 480
25 600Y
SL250, 250 A
SL400, 400 A
SL800, 800 A
SL800M5, 800 A
SL1200P5, 1200 A
1
SL1200P6, 1200 A
1
SL1200P7, 1200 A
1
S33931, 1200 A
1
HD/JD 2, 3 150/250
25 240
18 480
14 600
HG/JG 2, 3 150/250
65 240
35 480
18 600
HJ/JJ 2, 3 150/250
100 240
65 480
25 600
HL/JL 2, 3 150/250
125 240
100 480
50 600
HR/JR/KI 2, 3 150/250/250
200 240
200 480
100 600
Table 9: Short Circuit Current Ratings for Plug-On Lugs with
Protective Circuit Breakers (continued)
Catalog Number
and Ampere
Rating
Protecting Circuit Breakers
Maximum Available
Short Circuit Current
Catalog
Prefix
Number
of Poles
Maximum
Amperes
RMS Sym.
kA
Volts AC
80043-808-01.book Page 52 Wednesday, March 22, 2017 12:31 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Square D I-Line and is the answer not in the manual?

Square D I-Line Specifications

General IconGeneral
Bus MaterialAluminum or Copper
Voltage Rating600V AC
Current RatingUp to 1200A
EnclosureNEMA 1
Poles2, 3
Interrupting Rating200 kA (depending on the specific model and installed breakers)