Commissioning
7
Terminal Boxes for I.S. Circuits
8150/2
9 Commissioning
Before commissioning into service
Make sure that the device is not damaged.
Make sure that the device is installed correctly.
Make sure that the connections have been correctly made.
Remove any foreign objects from the device.
Check the tightening torques.
Check if all covers and partitions on live parts are in place and have been fixed.
10 Maintenance
10.1 Cleaning
Use only a solvent-free household detergent added to the cleaning water.
10.2 Repairs and maintenance
Only authorized and trained personnel should perform repairs and maintenance work on
hazardous location equipment.
The following details must be checked during maintenance:
X Cables are held securely in place by the entry hardware.
X Damage to the enclosure, cover gaskets and terminals.
11 Accessories and Spare Parts
11.1 Conduit hub with „Increased Safety“ ground terminal
WARNING
All unused enclosure openings must be closed using approved close-up plugs with
standard locknuts. (see section 11.2)
WARNING
Use only the following accessories in order to maintain the environmental ratings.
14795E00
Size Ordering Code
1/2″ 8166/11-01-NE
3/4″ 8166/11-02-NE
1″ 8166/11-03-NE
1-1/4″ 8166/11-04-NE
1-1/2″ 8166/11-05-NE
2″ 8166/11-06-NE