INsTALLATIoN
Commissioning
www.stiebel-eltron.com LWZ130 | 45
ENGLISH
Window contact
You can connect a window contact to terminal X18. The window
contact is required for passive cooling. The appliance checks
whether a window contact is connected and activated at X18.
The window contact must be an N/O contact.
10.5 Overflow apertures
Create suitable overflow apertures in the supply air area or over-
flow area. This is absolutely essential, since otherwise passive
cooling is not possible.
11. Commissioning
!
WARNING Injury
If the unit is switched on without the air ducts connected
and someone reaches through the air connectors into the
unit, there is a risk of injury.
Do not commission the unit until the air ducts are firmly
connected to it.
!
Material losses
Never operate the appliance without filters.
!
Material losses
Never operate the ventilation system if there are high lev-
els of dust inside the building or outside in the immediate
vicinity, as this could block the filter. Dust is created by
cutting tiles or working with plasterboard, for example.
11.1 Initial start-up
f To access the parameters, press the “MENU” button.
Display Description
P1 - Pxx
Parameter
I1 - Ixx
Actual values
Pro
Programs
Cod
Entry of the code for unlocking protected parameters and actual
values
f Enter 1000 to enable actual values and parameters which are
reserved for qualified contractors.
Enable fan
The fans are deactivated in the delivered condition.
f P28 : Set the parameter to "On".
Setting air flow rates
f Use parameters P6 to P9 to set the air flow rates for the fan
stages.
Date
f Set the current day of the week.
P80 1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
Time
f Set the current time.
P81 00:00 - 23:59
11.2 Recommissioning
f Check whether filters are fitted in the appliance. Never oper-
ate the appliance without filters.
f Check whether the condensate drain hose is damaged or
kinked.