3.13 Routing air hoses
The air hose can be extended by turning the Bowden cores into each
other. There should be approx. 30cm overlap. The total length of hoses
on the air inlet and outlet side must not exceed 8 m.
Never incorporate more than four 90° bends. The radius of the bends
must be at least 600 mm wide (relative to the middle of the hose).
» Cut to size using a sharp knife. The Bowden core can be cut with wire
cutters.
» Secure the air hose at approx. 1 m intervals. This prevents the hose
sagging because of its flexibility.
» Match the air hose ends to the shape of the oval connectors at the
hood and the hose connection plates. The hose connection plates are
available as accessories.
2
3
1
4
5
C26_03_01_0930
1 Hose connection plate
2 Hose clip (oval)
3 Air hose
4 Hose clip (oval)
5 Hood
Hose connection plate dimensions
1200
688
304
800
C26_03_01_0929
!
Risk of damage
Always cover the external apertures with wire grilles, and
secure the hoses against slippage.
3.14 Fitting air hoses
The example below shows the air hose connection being fitted.
26_03_01_1446
» Firstly, push the outer hose slightly upwards.
26_03_01_1447
» Push the inner hose halfway down onto the connector.
26_03_01_1448
» Seal the inner hose by affixing it to the connector using the fabric tape
provided.
26_03_01_1449
» Place the sealing strip provided around the connector.