3. CLEARANCES
-
IMPORTANT
STU
^
V
21
|
MODEL
SPECIFICATIONS
PAGE
5
When installed on a combustible floor surface the Stûv 21 firebox must be positioned on top of an 18mm cement
sheet floor plate and raised to a minimum height of 150mm using the appliance adjustable feet.
When installed on a non-combustible floor the fireplace can be installed directly onto the floor and adjusted in
height using the adjustable feet.
In a cavity built out of bricks, block work or 75mm ACC block the appliance must be installed with a minimum
gap of 50mm at the back and on
the sides.
In a cavity built out of silicate boards the appliance must be installed with a minimum gap of 100mm at the back
and on the sides.
Only non-combustible material (silicate board, Promatect H 12mm or brickwork) shall be used on the front wall
of the
cavity.
All internal framework above the appliance shall be made of non-combustible material.
The
cavity
above
the
appliance
must
be
capped
and
must
have
a
minimum
of
2500cm2
of
venting.
The appliance must be fitted with the standard triple skin flue.
To conform to the requirement of the joint AS/NZS 2918:2001 the appliance must be bolted down to comply
with the seismic restrain provisions.