8-20
Troubleshooting Guides
7005836 - Revision A - January, 2009
International Integrated
International Integrated
(ICB700 T
(ICB700 T
all)
all)
Series
Series
SEALED SYSTEM TROUBLESHOOTING / DIAGNOSTICS TABLES
NORMAL OPERATING PRESSURES TABLE NOTES:
• Only enter the sealed system to check pressures if the Error Code Troubleshooting Guide and General
Troubleshooting Guide could not pinpoint the cause of the temperature problem.
• Always use solder-on process valves when entering the sealed system. Do NOT use bolt-on process valves as
they are prone to leak.
• Whenever servicing the sealed system, the high-side filter-drier MUST be replaced.
• Pressures listed below are not indicative of initial pull down, but rather of a steadily running and properly function-
ing appliance.
• Pressures listed are for reference only, as actual pressure readings may vary because of one or more of the fol-
lowing reasons:
1. Ambient temperatures (Pressures are based on a 21°C (70°F) Ambient).
2. Temperature set-points (Pressures listed below are based on set-points of -18°C (0°F) in freezers and 3°C
(38°F) in refrigerators)
3. Food load quantity and temperature.
4. Condenser cleanliness.
5. Whether or not one or both refrigeration systems are operating.
6. Gauge calibration.
NORMAL OPERATING PRESSURES
Model Normal Low-Side Pressures Normal High-Side Pressures
ICB700TC/I
ICB700TR
ICB700TF/I
ICB736TC/I
ICB736TR
Refrigerator
Freezer
Upr Refrig.
Lwr Refrig.
Refrigerator
Freezer
Upr Refrig.
Lwr Refrig.
0 - 12 psi to 30 - 42 psi
5” Vac - 1 psi to 6 - 12 psi
0 - 12 psi to 30 - 42 psi
0 - 12 psi to 30 - 42 psi
5” Vac - 1 psi to 6 - 12 psi
0 - 12 psi to 30 - 42 psi
5” Vac - 1 psi to 6 - 12 psi
0 - 12 psi to 30 - 42 psi
0 - 12 psi to 30 - 42 psi
75 psi to 110 psi
75 psi to 120 psi
75 psi to 110 psi
75 psi to 110 psi
75 psi to 120 psi
75 psi to 110 psi
75 psi to 120 psi
75 psi to 110 psi
75 psi to 110 psi