SZ-CR2 22
Function: To set reset mode for Compressor2 output, on
Compressor2 HP Fault Digital Input.
If this parameter is set to,
(0)
= Auto Reset Option for HP Fault.
(1)
= Manual Reset Option for HP Fault
after H42 retrials in 1 Hour.
Example:
If user has set the parameter to following:
= HP Fault will get cleared automatically
once the Input becomes healthy.
= If this parameter is set to and H42
parameter is set to 5 then if the Compressor
gets tripped on HP fault for 5 times in 1
hour, controller will go into Manual Reset
and user has to reset the fault through RST
key by pressing for 2 Seconds. Fault will get
cleared only if the Input has become
Healthy.
Note:
This parameter is considered only if H02 is enabled
and CS is not equal to C1.
Min.
Max.
Fac.
Function: No of retrials of Compressor2 HP Fault Digital
Input when Manual Reset is selected.
Example: If this parameter is set to 5, Compressor will go
into Manual Reset if the HP fault occurs 5 times in an
Hour.
Note:
The Fault counts will get cleared in every hour.
This parameter is considered only if H02 is enabled
and CS is not equal to C1.
Min.
Max.
Fac.
1
10
5