Function: To activate/deactivate Compressor2 LP Fault
Digital Input.
If this parameter is set to,
= Digital input is disabled.
= Digital input is open connection (0V)
will be a fault.
= Digital input is close connection (230V)
will be a fault.
Note:
• This parameter is not considered only if CS = C1.
Function: Compressor2 LP Fault Digital Input Sensing
Delay. (Surge)
Example: If LS2 is set to 5 seconds, once the Compressor2
is ON, controller will ignore the LP Fault for 5 Seconds.
Note:
• This parameter is considered only if L02 is enabled
and CS is not equal to C1.
Function: Compressor2 LP Fault Digital Input Sensing
Delay. (Normal)
Example: If Ln2 is set to 5 seconds, once the Compressor2
is ON, if the LP Input is unhealthy for continuous 5
seconds, controller will trip the Compressor on LP Fault.
Note:
• This parameter is considered only if L02 is enabled
and CS is not equal to C1.
Function: To set reset mode for Compressor2 output, on
Compressor2 LP Fault Digital Input.
If this parameter is set to,
= Auto Reset Option for LP Fault.
= Manual Reset Option for LP Fault after
L42 retrials in 1 Hour.
Example:
If user has set the parameter to following:
= LP Fault will get cleared automatically once
the Input becomes healthy.
= If this parameter is set to and L42
parameter is set to 5 then if the Compressor
gets tripped on LP fault for 5 times in 1 hour,