SZ-CR2 24
Dd
controller will go into Manual Reset and
user has to reset the fault through RST key
by pressing for 2 Seconds. Fault will get
cleared only if the Input has become
Healthy.
Note:
This parameter is considered only if L02 is enabled
and CS is not equal to C1.
Function: No of retrials of Compressor2 LP Fault Digital
Input when Manual Reset is selected.
Example: If this parameter is set to 5, Compressor will go
into Manual Reset if the LP fault occurs 5 times in an Hour.
Note:
The Fault counts will get cleared in every hour.
This parameter is considered only if L02 is enabled
and CS is not equal to C1.
Min.
Max.
Fac.
1
10
5
Function: To activate/deactivate Compressor2 SPP Fault
Digital Input.
If this parameter is set to,
(0)
= Digital input is disabled.
(1)
= Digital input is open connection (0V)
will be a fault.
(2)
= Digital input is close connection (230V)
will be a fault.
Note:
This parameter is not considered only if CS = C1.
Min.
Max.
Fac.
dd
Function: Time delay to switch OFF the Light.
This parameter is used to set the time delay to
automatically switch OFF the light. If LD is set to 0 then
this parameter is disabled.
If this parameter is set to 7 minutes then, when light is
switched ON after 7 minutes it will be switched OFF
automatically.
Min.
Max.
Fac.
0 Min
30 Min
7 Min