SZ-CR2 28
Function: Set Temperature unit selection in °C or °F.
When set to,
(0)
= All parameters will be converted to
their FS values in °C.
(1)
= All parameters will be converted to
their FS values in °F.
Example:
If the Fac. Value of SP1/SP2 = 0°C, CF is changed from C to
F, then SP1/SP2 will become 32°F.
Min.
Max.
Fac.
Function: To set Controller Resolution.
When set to,
0.1 (0)
= It will take all parameter in 0.1°C
resolution.
1 (1)
= It will take all parameter in 1°C
resolution.
Note:
Temperature and Temperature related parameters
will also change accordingly.
This parameter is considered only if CF is not set to
Min.
Max.
Fac.
0.1
1
-
Function: To set Change Password.
User cannot enter into Program Mode & Set Mode, if
correct password is not entered.
If the password is kept other than 0, user need to enter
correct password to enter into Set/Program Mode.
If password is 0, user can directly access Set/Program
Mode.
Min.
Max.
Fac.
-999
999
0
Function: Keypad Lock.
This parameter is used to lock the keypad so that
tampering is not possible by by-standers.
(0)
= Deactivates Keypad Lock.
(1)
= Activates Keypad Lock.
This parameter can lock the keypad so that tampering is
not possible by-standers. When locked all parameters can
only be viewed, but not modified.
Min.
Max.
Fac.
dd