Function: To set Ht or Lt Power ON Delay for Alarm.
Example: If this parameter is set to 20 Minutes, once the
controller is powered ON, no fault Indication will be
activated for 20 Minutes.
Alarm delay is used only for High Temperature and Low
Temperature, but not for other faults.
Note:
This parameter is considered only if AL is not equal to
.
Function: Time Delay to activate Alarm Relay at Door
Open.
Example: If this parameter is set to 60 Sec, on door open
fault alarm relay and its icon will be ON after 60 Sec on
occurrence of door open fault.
Note:
• If AL is , this parameter will not be
applicable.
• If do0 is , this parameter will not be
applicable.
When this parameter is set to,
= Don’t save Power Off Status.
Function: Set display at Power Off Mode
When this parameter is set to,
= Display will be blank, only LED’s will
be ON as per condition.
= Display will show Temperature.
Note:
This parameter is considered only if Po is not equal to
.