SZ-CR2 26
Function: Display during Defrost.
When this parameter is set to,
(0)
= Control Probe Temperature.
(1)
= Defrost Label.
Note:
This parameter is considered only if P71, P72 are not
equal to 0.
Min.
Max.
Fac.
Function: Default (Normal) Display.
When this parameter is set to,
(0)
= Control Probe Temperature.
(1)
= Compressor1 Set Point.
(2)
= Compressor2 Set Point.
Min.
Max.
Fac.
Function: Display Delay.
Example: If this parameter is set to 1, Temperature on the
display will be updated after 1 Second. The same value
will be considered for calculation and logging.
Display delay parameter is applicable only when
Temperature is increasing (rising). When Temperature is
decreasing (falling) this parameter will not be applicable.
If this parameter is set to 0, this feature will be disabled.
Min.
Max.
Fac.
0 Sec
180 Sec
0 Sec
Function: To activate Alarm Relay.
When this parameter is set to,
(0)
= Alarm Relay is Disabled.
(1)
= Alarm Relay will be active for both Ht,
Lt and other faults.
(2)
= Alarm Relay will be active for Ht and
other faults except Lt.
(3)
= Alarm Relay will be active for Lt and
other faults except Ht
Min.
Max.
Fac.
Dd