EasyManua.ls Logo

Sub-Zero Wolf ICB700 Series - Page 82

Sub-Zero Wolf ICB700 Series
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 82
8-16
Troubleshooting Guides
7011902 - Revision A - October, 2009
International Integrated
International Integrated
(ICB700 Base)
(ICB700 Base)
Series
Series
ICB700BR
0 - 12 psi to 30 - 42 psi 75 psi to 110 psi
ICB700BF/I
5” Vac - 1 psi to 6 - 12 psi 75 psi to 120 psi
SEALED SYSTEM TROUBLESHOOTING / DIAGNOSTICS TABLES
NORMAL OPERATING PRESSURES TABLE NOTES:
Only enter the sealed system to check pressures if the Error Code Troubleshooting Guide and General
Troubleshooting Guide could not pinpoint the cause of the temperature problem.
Always use solder-on process valves when entering the sealed system. Do NOT use bolt-on process valves as
they are prone to leak.
Whenever servicing the sealed system, the high-side filter-drier MUST be replaced.
Pressures listed below are not indicative of initial pull down, but rather of a steadily running and properly function-
ing appliance.
Pressures listed are for reference only, as actual pressure readings may vary because of one or more of the fol-
lowing reasons:
1. Ambient temperatures (Pressures are based on a 21°C (70°F) Ambient).
2. Temperature set-points (Pressures listed below are based on set-points of -18°C (0°F) in freezers and 3°C
(38°F) in refrigerators)
3. Food load quantity and temperature.
4. Condenser cleanliness.
5. Whether or not one or both refrigeration systems are operating.
6. Gauge calibration.
NORMAL OPERATING PRESSURES
PRESSURE INDICATIONS
If low-side pressure is
NORMAL
LOW
LOW
HIGH
HIGH
& high-side pressure is
NORMAL
LOW
HIGH
LOW
HIGH
possible problem is
MECHANICAL
(see General Troubleshooting Guide)
LEAK
RESTRICTION
INEFFICIENT COMPRESSOR
OVER CHARGE
Model Normal Low-Side Pressures Normal High-Side Pressures
ICB700BC/I
5” Vac - 1 psi to 6 - 12 psi 75 psi to 120 psi

Related product manuals