User Manual US-EN    SR 10-480 AC 
Subject to EAR. ECCN EAR99 and related export control restrictions. 
  The dryer does not 
drain the condensate. 
  The condensate drain service valve is closed - open it. 
  Condensate strainer is clogged – remove and clean it. 
  The drain solenoid valve is jammed – remove and clean it. 
  Verify the electric wiring. 
  The coil of the drain solenoid valve is failed – replace it. 
  Electronic instrument is faulty – repace it. 
  The DewPoint is too low - the condensate is frost and blocks the air - see specific point. 
  Inlet compressed air pressure is too low and condensate is not drained – restore nominal conditions. 
  The SULLIMAX condensate drain does not work properly (see SULLIMAX MANUAL). 
  Failure during the 
condensate 
discharge. 
  The drain solenoid valve is jammed – remove and clean it. 
  Try to remove the electric connector on the solenoid valve - if drain stops verify the electric wiring or 
the electronic instrument is faulty - replace it 
  Please read the separate SULLIMAX installation and operating instructions. 
  The dryer does not start – see the corresponding point. 
  If installed - untreated air flows through the bypass unit – close the bypass. 
  The dryer does not drain condensate – see the corresponding point. 
  Dew point too high – see the corresponding point. 
  If installed: the HPS 
high-pressure switch 
has triggered. 
  Check which of the following reasons is responsible for the triggering: 
1.  The ambient temperature is too high or the room ventilation insufficient – ensure 
sufficient ventilation. 
2.  The condenser is dirty – please clean it. 
3.  The condenser fan does not work – see the corresponding point. 
  Reset the pressure switch by pressing the button on the controller itself – check the proper 
functioning of the dryer. 
  The HPS pressure switch is defective – contact a SULLAIR service technician for the replacement. 
  If installed: 
the LPS low-pressure 
switch was triggered. 
  There is a leak in the refrigeration cycle – please contact a SULLAIR service technician. 
  The pressure switch is automatically reset as soon as the normal conditions are re-established – 
check the dryer for proper functioning.