SRC Service Manual
Revision 02
Aug 2007
7.4 Factory Parameter List
Factory parameters are locked and can only be modified by entering a special
code reserved for authorized factory trained technicians. Altering these
parameters may significantly effect dryer operation and could allow operating
conditions which are unsafe or damaging to personnel and/or equipment.
Altering the values of these parameters by anyone other than a trained
authorized factory technician, or without the express written authorization of the
factory, will void warranty. Contact Sullair for further information.
!
Parameter Description Units Min Max Default
A7 High Dewpoint Warning Delay at Startup min 0 60 15
A8 Low Dewpoint Alarm Setting
o
C -9.9 10 0
B4 Reset Working Hours - 0 (no) 1 (yes) 0 (no)
B5 Coolant Tank Temperature
o
C/
o
F - - -
B6 Disable Access to Factory Parameters - 0 (no) 1 (yes) 0 (no)
B7 Reset Alarm Report - 0 (no) 1 (yes) 0 (no)
C1 Coolant Temperature Setting
o
C -9.9 70 1
C2 Coolant Temperature Differential
o
C 0 30 1
C3 Compressor OFF Time Delay sec 0 600 1
C4 Immediate Compressor OFF Temp
o
C -9.9 15 0.5
C5 Software Identifier - d.t.1 d.t.1 d.t.1
C6 Compressor ON Time Delay sec 0 900 60
D4 Drain Open Delay sec 0 900 60
D5 Drain Close Delay (Normal Cycle) sec 0 120 5
D6 Drain Close Delay (Extended Cycle) sec 0 300 10
D7 Extended Cycle Interval* - 0 900 100
D8 Drain Alarm Setting* sec 10 900 30
For further information on how the “C” parameters affect cycling operation, refer to Section 8.
For further information on how the “D” parameters affect drain functioning, refer to Section 9.