EasyManua.ls Logo

Sunquest SQ-2220 - Page 6

Sunquest SQ-2220
14 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
3 b) Installation: one system on rack or roof. (Horizontal only)
1 - Mounting kit (part # SQ-RMK5) is required
Diagram Step 3b
Using a utility knife or a hand saw, cut rubber hose (SK-FTG-J) in half. Make sure
you cut it as straight as possible. See Fig 3b-1. You should now have two rubbers
3 ¾" long.
Apply Teflon on two of the caps (SK-FTG-F). See Fig 3a-1.You only need 2 of the 4
caps for this type of installation.
Thread the 2 caps into the panels as per Diagram Step 3b. Do not over tighten.
See Fig 3a-2
Put "O" rings (SK-FTG-I) on both combination adapters (SK-FTG-D). See Fig 3a-3
Thread both combination adapters into the panels as per Diagram Step 3b.
Do not over tighten. See Fig 3a-4
Push the rubber hose you cut in half previously over the panel header as per Diagram
Step 3b. Slide a metal collar (SK-FTG-L) onto the rubber hose. Place metal collar
1
/
4
"
from edge and tighten collar with screwdriver. See Fig 3a-5. Repeat for other end of panel.
Slide another metal collar onto the rubber hose. Connect the 2 panels together by pushing
the rubber hose over the second panel header. Tighten metal collar to secure assembly.
See Fig 3a-6. Repeat for other end of panel.
Install mounting kits as per instructions included with them. Panels must be installed with a slight
slope (minimum 1 inch per 10 feet) toward the inlet. This will allow the panel to drain properly.
Note: The inlet must always be at the lower end of the panel and the outlet at the higher end of the panel.
Combination Adapter
Cap
Cap
Rubber hose
3.75"
Rubber hose
3.75"
Combination Adapter
Fig 3b-1
Inlet
Outlet
A Minimum of 1 inch fall per 10 feet

Related product manuals