EasyManua.ls Logo

suntouch FloorStat 500500-120 User Manual

suntouch FloorStat 500500-120
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
MODEL 500500-120 (120 VAC)
SUMMARY
TO CHANGE THE TEMPERATURE SCALE FROM °C (CELSIUS)
TO °F (FAHRENHEIT) AND BACK
Switch the dip switch on the back of the control to either °C or °F.
Note: The other three dip switches are not used.
TO SET TEMPERATURE
Press on or once to see setpoint temperature appear on
display. Every subsequent press will change the setpoint tempera-
ture by one degree.
TO RECORD THE (COMFORT) SETPOINT TEMPERATURE
Select chosen setpoint temperature by using or button. Press
on button (2 to 3 seconds) until icon appears on display.
TO RECORD THE (ECONOMIC) SETPOINT TEMPERATURE
Select chosen setpoint temperature by using or button. Press
on button (2 to 3 seconds) until icon appears on display.
CHECKING GROUND FAULT CIRCUIT INTERRUPTER (GFCI)
Adjust the setpoint temperature until heating indicator (flames)
appears on display. Press TEST button. The test is conclusive if the
warning light (GFCI) on thermostat is ON and power to the load is
cut-off (flames remain on display though). If these events do not
occur, check the installation. Press on RESET button to reset the
GFCI.
INSTALLATION
Parts included:
One (1) 500500-120 (120 VAC) thermostat
Two (2) 6-32 screws
Four (4) Solderless connectors (for copper wire)
One (1) Temperature sensor with a 15-foot extension
TURN OFF POWER TO THE HEATING SYSTEM AT THE MAIN
POWER PANEL TO AVOID ELECTRICAL SHOCK. KEEP AIR VENTS
OF THE THERMOSTAT CLEAN AND FREE OF OBSTRUCTIONS.
This thermostat should be installed by an electrician or experienced
technician. The thermostat must be used with a self-protected
heating system equipped with a thermal cut-off and circuit breaker or
fuse.
This thermostat was designed to control floor electric heating
systems. The resistive load must not exceed 1920 watts at
120 VAC (16.0 A). The thermostat is equipped with a ground
fault circuit interrupter (GFCI) and therefore the isolation of the line
and load is required for operation. The polarity of line connection
must be respected. During a ground fault, only the current in
the black wire of the load will be cut-off. Connect thermostat as
shown on diagram.
1. CONNECTING WIRES AND MOUNTING THERMOSTAT
Connect the rear thermostat wires to the power supply and to the
load using solderless connectors for copper wires. See schematic
diagram below.
Push the excess wire back into the electrical box to prevent interfer-
ence withthe thermostat. Secure the thermostat using two (2)
6-32 screws 1-1/4 inches long. Once the thermostat is properly
installed, return power to heating system.
2. CONNECTING TEMPERATURE SENSOR WIRE
Connect the sensor wire to the two lower screws of the terminal
block at the back of the thermostat (no polarity need to be
respected). The wire must pass outside the electrical box and follow
the wall down to the floor. The sensing probe should be placed in a
representative heat area for maximum system perfomance. The
sensing probe should be centered between the wires in the mat.
The probe wire cannot cross any heater wires and the temperature
sensor must not be directly or adjacent to a heating wire.
VAC
120
60 HZ
VAC
120
60 HZ
720-111715
920-111-014-00-1-A
1/2
Question and Answer IconNeed help?

Do you have a question about the suntouch FloorStat 500500-120 and is the answer not in the manual?

suntouch FloorStat 500500-120 Specifications

General IconGeneral
Brandsuntouch
ModelFloorStat 500500-120
CategoryThermostat
LanguageEnglish

Summary

Thermostat Summary

Temperature Scale Conversion

Switch the dip switch on the back of the control to either °C or °F.

Setting Temperature

Press on or once to see setpoint temperature appear on display. Subsequent presses change setpoint by one degree.

Recording Comfort Setpoint

Select chosen setpoint temperature by using or button. Press on button until icon appears.

Recording Economic Setpoint

Select chosen setpoint temperature by using or button. Press on button until icon appears.

GFCI Test Procedure

Check GFCI by pressing TEST button when heating indicator appears. Observe warning light and load cutoff.

Installation and Wiring

Connecting Wires and Mounting

Connect rear thermostat wires to power supply and load using solderless connectors. Secure thermostat with screws.

Connecting Temperature Sensor Wire

Connect sensor wire to lower screws of terminal block. Route wire to floor probe in representative heat area.

Power Up and Thermostat Operation

Initial Power Up Display

When power is applied, display shows floor temperature. Check for warning light and error messages.

GFCI Test During Operation

Perform GFCI test monthly. If test fails, check load wires and installation. Cut power if warning light is on.

Setting and Recalling Setpoints

Use buttons to set temperature. Press and hold to record Comfort/Economic setpoints. Recall by pressing buttons.

Temperature Scale Selection

Choose °C or °F display by pressing the button while pressing and releasing RESET.

Technical Specs and Warranty

Thermostat Specifications

Details model, supply, load, GFCI class, approvals, display/setting ranges, storage, and regulation.

Limited Warranty Information

Details one-year limited warranty for material defects and workmanship. Excludes transport, misuse, accidental damage.

Related product manuals