Sutron Corporation 8310 & 7310 Users Manual 8800-1125Rev. 2.7 (BETA) 4/16/2014 pg. 167
Input. Be sure to use a reference resistor with a tight enough tolerance to achieve the accuracy
in temperature you desire.
Measurement Setup
Converting the thermistor resistance to temperature is typically done with the Steinhart-Hart
equation, shown below. T is temperature in Kelvin, R is the thermistor resistance in Ohms, and
A, B, and C are constants corresponding to the thermistor, usually supplied by the vendor.
Alternatively, if the vendor supplies a table of resistance vs. temperature, use a Lookup Table for
processing.
Field
Value
InputType
Resistance
Module
1
Channel
Analog Input port number
where Signal 1 is wired
Differential
No
FullScale
0-5V/+-2.5V
Resistor
Resistance value, in Ohms,
of reference resistor
SettlingTime
100
FilterNotch
60
SwitchedPwr
None
Processing
Steinhart-Hart
A
Steinhart-Hart coefficients
corresponding to
thermistor
B
C
Cal Slope
1
Cal Offset
0