Function parameter description NICE3000 User Manual
152
C. External call for current oor opening the door: After the lift close the door, the current oor
has the re-opening function.
D. Open the door when stops: When the lift stops, its judged according to several conditions:
If theres only single side external call, the lift stops and opens the door that is calling; If there
are two sides external call, the lift stops and judges to open the door a
ccording to door1 and
door2 control switch; If theres no external call, but internal call, the lift judges to open the
door according to door1 and door2 control switch when the life stops;
E. After selection of this function, the highest oor of the fteenth oor (physical oor). External
call address 1~15 corresponds to Floor 1~15 door 1 external call, and external call address
17~31 corresponds
to Floor 17~31 door 2 external call.
6.16 FE Group Factory Parameters (Reserved)
6.17 FP Group User Parameters
FP-00
User password Default 0 Min. Unit 1
Setting Range 065535
Set any number but zero, the password protection function is valid.
00000: Clear the password value setting by previous user, and make the password protection
function invalidation.
After the user password is set and valid, when it gets into the parameter setting state, you
cant check or modify the parameters if the password is not correct. De
tails of password
setting measures are listed in section 4.2.4.
Please rmly remember your setting password, and contact with the factory if you miss-set or
forget.
FP-01
Parameter resetting Default 0 Min. Unit 1
Setting Range 012
0: None;
1: Return to factory parameters. All the values of other function parameters but F1 group
function code will return to factory parameters. Please operate with caution!
2: Clear memory parameter. It will clear all the recorded error information.
FP-02
User setting examination Default 0 Min. Unit 1
Setting Range 01
0: Invalidation
1: Valid, and the operation keyboard only displays those parameters different from factory
setting.