20170724 We reserve the right to alter specifications.
GLOBAL
1
BACnet support for up to 4 units with double flow and heat recovery equipped with TAC5 control boards and SAT ETH-
ERNET. The BACnet Standardized Device Profile (Annex L) of the BACnet device is: BACnet Application Specific Control-
ler (B-ASC). The supported Data Link Layer Options are BACnet / IP and MS/TP slave.
2. Standard objects supported
Object Type
Analog Input
Object_Identier, Object_Name, Object_Type, Present_Value,
Status_Flags, Event_State, Out_Of_Service, Units, Description.
Analog Value
Object_Identier, Object_Name, Object_Type, Present_Value,
Status_Flags, Event_State, Out_Of_Service, Units, Description.
Integer Value
Object_Identier, Object_Name, Object_Type, Present_Value,
Status_Flags, Event_State, Out_Of_Service, Units, Description.
Device
Object_Identier, Object_Name, Object_Type, System_Status,
Vendor_Name, Vendor_Identier, Model_Name, Firmware_Revision,
Application_Soware_Version, Protocol_Version,
Protocol_Revision, Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_List, Max_
APDU_Length_Accepted, Segmentation_Supported.
1. Overview
BACnet gateway