INSTALLATION
INSTRUCTIONS
MODEL 233P/111P/233P-1.5
Revision B1
Rapid City, SD, USA, 07/2009
II-111-233-15P-B
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Questions and Answers

  • A
    Ann WattsJul 31, 2025
    What to do if SymCom Control Unit PumpSaver®Plus shows OVERCURRENT?
    • J
      jasonespinozaJul 31, 2025
      If the SymCom Control Unit displays an OVERCURRENT message, it means the pump has shut off due to an overcurrent condition. The unit will automatically try to restart after a delay, assuming the line voltage is acceptable. You should check for low or high voltage, or jammed pump impellers. If these conditions aren't present, recalibrate the unit while it's drawing higher current, ensuring the amperage doesn't exceed the SFA.
  • P
    Patrick SandersAug 5, 2025
    What to do if SymCom Control Unit PumpSaver®Plus displays DRY RUN / DEAD HEAD?
    • T
      twallaceAug 5, 2025
      If your SymCom Control Unit displays a DRY RUN / DEAD HEAD error, it indicates the pump shut off because of a dry run or dead head condition. The unit is currently in a restart delay and will attempt to restart. You should check for any restricted flow or an inadequate supply of liquid to the pump.
  • X
    xhaydenAug 9, 2025
    Why SymCom Control Unit PumpSaver®Plus shows VOLTAGE FAULT?
    • Q
      qsotoAug 9, 2025
      The SymCom Control Unit displaying a VOLTAGE FAULT indicates that the pump is not starting because of voltage issues. The unit is actively monitoring the voltage and will remain in this state until the voltage reaches an acceptable level. If the unit remains in this state for more than 5 seconds, you should check for high or low voltage.
  • D
    Daniel GuerreroAug 13, 2025
    What to do if SymCom Control Unit is OFF / MANUAL RESTART?
    • J
      jeffrey90Aug 13, 2025
      If the SymCom Control Unit displays OFF / MANUAL RESTART, the pump isn't running. This could be because the PumpSaver®Plus tripped due to a dry-run, dead-head, or overcurrent while the RESTART DELAY/ CALIBRATION knob was in the RESET position, or because source power is absent. If the knob is in the RESET position, rotate it out of RESET. If the CAL light blinks, check for an overcurrent condition. If the RUN light blinks, look for a dry-run or dead-head condition. If no lights come on, check incoming power for adequate voltage.
  • L
    Lori SalinasAug 17, 2025
    How to fix RAPID CYCLE error on SymCom Control Unit PumpSaver®Plus?
    • H
      Holly NguyenAug 18, 2025
      If the SymCom Control Unit PumpSaver®Plus has shut down due to rapid cycling, you need to remove and reapply power to reset the unit. Then, check for a broken bladder in the pressure tank (if one is used) or a defective pressure or float switch.
  • J
    Jeff PriceAug 22, 2025
    What does RUN status mean on SymCom PumpSaver Plus 111P?
    • J
      Jeanette CooperAug 22, 2025
      The RUN status on the SymCom Control Unit indicates that the pump is running or ready to run, and there are no operational problems. If the pump is not running, check for loose wiring and ensure proper function of pressure or float switches.
  • V
    Vernon CarpenterAug 26, 2025
    What does CAL COMPLETE mean on SymCom PumpSaver Plus 111P and how to restart pump?
    • J
      josephjonesAug 26, 2025
      The CAL COMPLETE status on the SymCom Control Unit means the unit has finished calibration, but the RESTART DELAY/ CALIBRATION knob was left in the CAL position, causing the pump to remain off. The pump will restart as soon as the RESTART DELAY/ CALIBRATION knob is rotated out of the CAL position.

Summary

CONNECTIONS

Wiring Diagram References

Lists wiring diagrams for typical, 3-wire, deluxe, and 2-wire applications.

OPERATION

CALIBRATION

Calibrating While Pumping

Explains how to calibrate the unit while the pump is running.

Sensitivity Adjustment

Details adjusting the underload trip sensitivity for protection.

Reset Mode and Restart Delay

Describes manual reset and restart delay settings for the unit.

RUN HOURS; FAULT HISTORY

Resetting Run Hours and Fault History

Provides instructions for clearing recorded pump run hours and fault history.

RAPID CYCLING

Line Side; Upstream Rapid Cycling

Discusses rapid cycling detection on the input side and its reset procedure.

Enabling Line Side Rapid-Cycle Protection

Outlines the procedure to enable rapid-cycle protection for upstream control devices.

RAPID CYCLING (Load Side; Downstream)

USING AN INFORMER

TROUBLESHOOTING

Indicator Light Status Interpretation

Explains the meaning of indicator light combinations for problem diagnosis.

Common Pump Operation Faults

Details diagnosis and correction for dry-run, dead-head, overcurrent, and voltage faults.

Rapid Cycle Fault Diagnosis

Describes how to identify and resolve rapid cycling issues.

PHYSICAL DIMENSIONS

SPECIFICATIONS

SymCom PumpSaver Plus 111P Specifications

General IconGeneral
Model111P
Input Frequency50/60 Hz
Motor Voltage Range190-480 VAC
Phase3-phase
Motor HP Range1-100 HP
Enclosure RatingNEMA 1
Operating Temperature-40° to 140°F (-40° to 60°C)
Max Load Current5A
Over/Under Voltage TripAdjustable
Voltage Unbalance TripAdjustable
Protection FeaturesVoltage Unbalance, Phase Loss, Phase Reversal
Reset TypeAutomatic/Manual
MountingPanel
Weight1.1 lbs
Restart DelayAdjustable
Output ContactsSPDT
Input Voltage190-480 VAC
Operating Voltage190-480 VAC
Trip DelayAdjustable 0.1-30 seconds