D150-02-00 1 I56-598-03R
B114LP Plug-in Detector Base
For use with the following smoke detectors:
IN US: 1151, 2151
IN CANADA: 1151A, 2151A
IN EUROPE: 1151E, 2151E
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue
St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors. This man-
ual provides detailed information on detector spacing,
placement, zoning, wiring, and special applications, and is
available at no charge from System Sensor. (For installation
in Canada, refer to CAN/ULC-S524, Standard for the
Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.
Specifications
Base Diameter: 6.2 inches (157 mm)
Base Height: 0.95 inches (24 mm)
Weight: 0.6 lb. (274 g)
Mounting: 4-inch square box with or without plaster ring. Min. depth–1.5 inches
4-inch octagon box. Min. depth–1.5 inches
Operating Temperature Range: to 49°C (32° to 120°F)
Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Electrical Ratings - includes base and detector
System Voltage: 120 VAC, 60 Hz
Relay Contact Ratings
Resistive or Inductive (60% power factor) load
Form A: 2.0A @ 30VAC/DC
Form C: 2.0A @ 30VAC/DC
0.6A @ 110VDC
1.0A @ 125VAC
Start-up Time: 36.0 Seconds maximum
(After 60 second reset)
General Description
The model B114LP detector base is designed for use with
System Sensor model 2151 photoelectronic and 1151 ioniza-
tion detector heads. This four-wire base is equipped with
screw terminals for the connection of power, ground, relay
connections, and an optional RA400Z remote annunciator.
It also includes a resistor that limits current when the asso-
ciated smoke detector is in the alarm state.
Mounting
The detector base mounts directly to 3-1/2 inch and 4-inch
octagon boxes and 4-inch square boxes, with or without
plaster rings. To mount the base, remove the decorative
ring by rotating it in either direction to unhook the snaps
before separating the ring from the base. Use the screws
supplied with the junction box to attach the base to the box
through the appropriate slots in the base.
See Figure 2. Position the decorative ring around the base
and rotate it in either direction until the ring snaps into
place.
Question and Answer IconNeed help?

Do you have a question about the System Sensor B114LP and is the answer not in the manual?

System Sensor B114LP Specifications

General IconGeneral
ColorWhite
MaterialPlastic
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
Alarm ResetAutomatic

Summary

General Description

Product Overview

The B114LP detector base is designed for System Sensor models 2151 photoelectronic and 1151 ionization detector heads.

Mounting

Mounting Procedure

The detector base mounts to 3-1/2 and 4-inch octagon or square boxes; remove decorative ring to access mounting screws.

Installation Guidelines

Loop Resistance and Wiring

Ensure compatible loop resistance and follow NEC/local codes. Use twisted pair wiring for power loop.

Wiring Instructions

Supervised Connections

Cut wires at terminals 8, 9, 10, 11 for supervised electrical connections, do not loop.

Tamper-resistance Feature

Activating and Removing

Make base tamper resistant by breaking a tab; removal requires a tool to press a plastic lever.

Three-Year Limited Warranty

Warranty Coverage

System Sensor warrants the base against defects in materials/workmanship for three years from manufacture date.