5.6.4TA2000-4500HW
Connectionblock,besidethetransformer,marked160V,240V,320Vand400Vfor400V3~(90V,140V,
185V,230Vfor230V3~)isusedtosetthefanspeed.
Defaultsettingsforhighfanspeedareonterminalpost400V(230V)andlowfanspeedonterminalpost
240V(140V).Whenreconnectingtoanotherfanspeedboththecablesforhigh/lowfanspeedmustbe
moved.E.g.toreducethehighfanspeedonestepthecablesconnectedtothetwoterminalpostsmarked
400V(230V)aretobemovedtothetwoterminalpostsmarked320V(185V).
*=Highfanspeed
**=Highfanspeed400V
***=Highfanspeed230V
TA450-4500Installationinstructions
132615