Mainmenuitem
Sub-menuitem1Sub-menuitem2
Explanations
Firedamper
Auto
SettheFiredampertoAuto,
OpenorClose
Note:
Needstobeactivatedinorder
tobevisiblehere
Congurationofredamper
functionsaremadeat
Administratorlevel
Outdoorair
damper
Auto
SettheOutdoorairdamperto
Auto,OpenorClose
Exhaustair
damper
Auto
SettheExhaustairdamperto
Auto,OpenorClose
Extrasequence
Y5
Auto
Manualset:
0.0
SettheExtrasequenceto
Auto,ManualorOff
→Settings
Inthismenugroupthesettings
fortheactivatedfunctionsare
available.Dependingonwhich
choiceshavebeenmadeinthe
congurationmenusomeofthe
possiblealternativesmaynot
bedisplayed.
→Controltemp
Supplyair
control
P-band:
33.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Supplyaircontrolfunction
Note:
SeeCorrigoEventilation
manualformoreinformation.
Roomcontrol
P-band:
100.0°C
I-time:300.0
sec
SetP-bandandI-timeforthe
Roomcontrolfunction
Note:
SeeCorrigoEventilation
manualformoreinformation.
Shutdownmode
P-band:
100.0°C
I-time:100.0
sec
SetP-bandandI-timeforthe
Shutdownfunction
Note:
SeeCorrigoEventilation
manualformoreinformation.
TopvexSR/TR03,SR/TR04,SR/TR06OperationandMaintenanceInstructions
206902
17
SystemairAB