Commissioning
|
13
Main menu item
Sub-menu item 1 Sub-menu item 2 Explanations
Outdoor comp.Setp.
1
—20°C = 0 Pa
10°C = 0 Pa
Act. Comp: 0 Pa
Set the EAF pressure compensation
for the settable outdoor
temperature. The outdoor
compensation is linear and is set
using two parameter pairs which
give the value of the compensation
at two different outdoor
temperatures. The compensation
can be positive or negative.
Shows the actual pressure
compensation.
Extra flow EAF
Actual: m³/h
Shows the extract air flow
→ Time settings
→ Time/Date
Set correct time and date.
Set 00:00 - 24:00 for continuous
running. Setting 00:00 - 00:00
inactivates the period (stops the
unit). Normal speed overrides
Reduced speed i.e. Normal speed
07:00 - 16:00 and Reduced speed
00:00 - 24:00 runs the unit on
Normal speed 07:00 - 16:00 and
Reduced speed the rest of the day.
→ Timer normal
speed
Normal speed
Monday
Per 1: 07:00–16:00
Per 2: 00:00–00:00→
Normal speed
Monday-Friday
Per 1: 07:00–16:00
Per 2: 00:00–00:00↓
Set week schedule Monday to
Sunday, Monday-Friday+ Holiday
for normal speed. Possible to set 2
periods per day.
Note the settings in the
commissioning record.
→ Timer reduced
speed
Reduced speed
Monday
Per 1: 00:00–24:00
Per 2: 00:00–00:00→
Reduced Speed
Monday-Friday
Per 1: 00:00–24:00
Per 2: 00:00–00:00↓
Set week schedule Monday to
Sunday, Monday-Friday + Holiday
for reduced speed. Possible to set 2
periods per day.
Note the settings in the
commissioning record.
→ Extended
running
Extended running
60 min
Time in ext. running
0 min↓
Set the time for extended running.
Use digital input to force the unit to
start or increase to normal running
even if the actual mode is Off or
Reduced.
If the running time is set to 0 the
unit only runs as long as the digital
input is closed.
The time the extended running is
active is monitored in "Time in ext.
Running".
It's also possible to set a time here
as well in order to shorten the
initial set period.
124455 | A003