EasyManua.ls Logo

t.a.c. Xenta 913 User Manual

t.a.c. Xenta 913
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
1 (4) 0-003-2711-0 (EN)
TAC Xenta
®
913
TECHNICAL DATA
Subject to modification.
LonWorks
®
Gateway
10 Mar 2004
Supply voltage ............................. 24 V AC ±20%, 50/60 Hz
.................................................................. or 19–40 V DC
Power consumption............................................... max 5 W
Transformer sizing ........................................................5 VA
Ambient temperature:
Storage .................... –20 °C to +50 °C (–4 °F to +122 °F)
Operation ................ ±0 °C to +50 °C (+32 °F to +122 °F)
Humidity............................. max. 90% RH non-condensing
Mechanical:
Enclosure ............................................................ ABS/PC
Enclosure rating ....................................................... IP 20
Flammability class, materials ........................... UL 94 V-0
Dimensions ................................................. see diagram
Weight ..................................................... 0.2 kg (0.44 lb.)
Real time clock:
Accuracy at +25 °C ........................ ±12 minutes per year
Power failure protection ............................................ 72 h
Communication:
A: RS232 ........................... 2400 – 57600 bps, RJ45, 8-p
A: RS485 .........2400 – 57600 bps, async. terminal block
B: RS232 .......................................................... RJ10, 4-p
C: RS485 ............................. sync. (SDLC) terminal block
L
ONWORKS ........................................... TP/FT-10, terminal block
Ethernet ..................................... TCP/IP, 10Base-T, RJ45
Agency Compliances:
Emission:
CE ..................................................................EN 50081-1
Immunity:
CE .............................................................. EN 61000-6-2
Safety:
CE ..................................................................EN 61010-1
UL 916..................................................... C-UL US Listed
Part numbers:
TAC Xenta 913 .............................................. 0-073-0835
Terminal part TAC Xenta 400 ....................... 0-073-0902
TAC Xenta: Programm. Serial Kit .................. 0-073-0920
The TAC Xenta 913 is a cost-effective way to integrate a
large variety of products into a TAC network. The TAC
Xenta 913 supports the most commonly-used open
protocols, like Modbus, BACnet and LonWorks. It also
supports some manufacturer-specific protocols.
2 3 4 5 6 7 8 10
12 13 14 15 16 17 18 20
48 ± 0,5
(1.89±0.02)
70 ± 2,0
(2.75±0.08)
10,1
(0.40)
Ø 4 (0.16)
90 (3.55)
110 (4.33)
77,4
(3.05)
45
(1.77)
The TAC Xenta 913 reads values from the target network
and transfers them to a LonWorks network. Configuration is
carried out using the TAC XBuilder programming tool.
Question and Answer IconNeed help?

Do you have a question about the t.a.c. Xenta 913 and is the answer not in the manual?

t.a.c. Xenta 913 Specifications

General IconGeneral
Brandt.a.c.
ModelXenta 913
CategoryGateway
LanguageEnglish

Summary

Technical Data

Agency Compliances

Lists Emission, Immunity, and Safety compliances including CE and EN standards.

Part Numbers

Details part numbers for the TAC Xenta 913 and related kits.

Dimensions and Weight

Provides physical dimensions and weight specifications with a reference diagram.

Real Time Clock

Specifies accuracy and power failure protection for the real-time clock.

Communication Interfaces

Details RS232, RS485, LONWORKS, and Ethernet communication specifications.

Overview of TAC Xenta 913 Functionality

Connecting BACnet to LonWorks

Illustrates BACnet to LonWorks integration via RS232 and IP networks.

Acting as a Modbus Master

Diagrams showing the TAC Xenta 913's role as a Modbus master over RS232/RS485.

Acting as a Modbus Slave

Diagrams showing the TAC Xenta 913's role as a Modbus slave over RS232/RS485.

Configuration and Installation Details

Open Protocol Driver List

Lists supported open protocols like BACnet, Modbus/JBUS, and LONWORKS.

Configuring the Device

Requirements for configuration using TAC XBuilder and Excel, plus documentation.

Installation and Connection

Details modular jacks, LEDs, reset button, and terminal connections.

Security and Web Interface

Covers secure configuration access via username/password and web interface.