Instruction Sheet
0015-MSF-IFC Multi-Speed Cartridge Circulator
with Integral Flow Check
102-433
APPLICATION:
Maximum operating pressure is 125 psi (862 kPa).
Maximum water temperature not to exceed nameplate rating.
Cast iron circulators are to be used for closed loop systems only.
Stainless steel circulators are to be used on open, potable water systems.
Taco Cartridge circulator pumps are for indoor use only employer uniquement a
l´interieur.
For use with water or maximum of 50% glycol/water mix systems only.
CAUTION: 1. The addition of petroleum based fluids or certain chemical additives to systems
utilizing TACO equipment voids the warranty.
2. Use supply wires suitable for 90°C ATTENTION: Employer des fils d´alimentation
adequats pour 90°C.
WARNING: To avoid electrical shock, disconnect the power supply to the circulator and the main
electrical unit.
WARNING: Do not use in swimming pool or spa areas; pump has not been investigated for this
application.
WARNING: In the event the electrical box has been pulled off of the housing, DO NOT attempt to
reattach it. Use of any other screw may short out the stator windings, creating a risk of
electrical shock.
CAUTION: When installing electrical connections, do not apply mechanical loads to the capacitor
box; otherwise, retaining screws may be pulled out of the housing, making circulator
unusable.
S
UPERSEDES: June 1, 2014 EFFECTIVE: August 10, 2015
Plant ID# 001-4002
CAUTION: Installations at higher elevations over 5000 feet must have higher fill pressure of 20 psi
minimum to prevent pump cavitation and flashing. Premature failure may result. Adjust
expansion tank pressure to equal fill pressure. A larger size expansion tank may be required.
INSTALLATION:
1. Location Install the
“OO” circulator on the supply side of the boiler “pumping away” from the expansion tank as shown in
Figure 1. This is the best pump location for optimum system performance and maintaining positive system pressure. An alter-
nate location is on the boiler return line as shown in Figure 2.
2. Mounting position Mount circulator with the motor in the horizontal position. It may be mounted vertically with the
motor up, provided that the system cold fill pressure is at least 20 psi (138 kPa) to ensure proper air purging and prevent
flashing.
3. Rotating body Body has an arrow on the front that indicates direction of flow. To rotate body, remove the four body
bolts, rotate body and replace bolts. Make sure that the junction box is NOT located underneath the circulator. (The
junction box must NOT be located in the 6 o’clock position, as viewed from the motor end.)
4. Electrical connections Observe all applicable codes when connecting to power supply.
The motor is thermally protected, and does not require additional overload protection.
Either colored wire from the capacitor box can be attached to either colored wire from the
power supply. There is no “hot” or “common” wire leading from the capacitor box. Typical
installation would be to attach the white wire to the white (common) power supply wire and
either the yellow or blue wire to the black (hot) power supply wire. The pump cannot run
backwards.
SPEED
Amps (Watts)
1 0.54 (58)
2 0.74 (79)
3 0.85 (98)
ELECTRICAL DATA
CAUTION: Do not use flat rubber gaskets on pump flanges. Only use O-ring gaskets provided or
leaking will result. Warranty will be void.
Question and Answer IconNeed help?

Do you have a question about the Taco Comfort Solutions 0015-MSF-IFC and is the answer not in the manual?

Summary

Product Application and Specifications

Application Guidelines

Specifies operating pressure, temperature, fluid compatibility, and use environment.

Safety, Warnings, and Cautions

Application Restrictions

Prohibits use in pools/spas and specifies indoor use requirement.

Electrical Safety

Covers risks of shock, proper wiring, and capacitor box handling.

System and Fluid Handling

Warns against additives, specifies glycol mix limits, and high-elevation advice.

Installation and Operation

Mounting and Location

Guides on preferred mounting position and orientation.

Electrical Connections

Details how to connect the circulator to the power supply.

System Filling and Air Purging

Provides steps for filling the system and purging air for optimal operation.

Circulator Speed Control

Explains how to set the speed dial for desired performance.

Service, Maintenance, and Performance

Performance Data

Includes performance curves and replacement model information.

Integral Flow Check (IFC) Service

Details the removal and replacement procedure for the IFC.

Component Replacement

Guides on replacing the motor assembly, cartridge, and capacitor.

Limited Warranty Statement

Warranty Terms and Limitations

Outlines the warranty duration, exclusions, and limitations.

Taco Comfort Solutions 0015-MSF-IFC Specifications

General IconGeneral
Model0015-MSF-IFC
CategoryWater System
Body MaterialCast Iron
Maximum Flow16 GPM
Minimum Fluid Temperature40°F
Maximum Fluid Temperature230°F
Maximum Working Pressure125 psi
Voltage115 V
Phase1
Hertz60 Hz
IFCYes
Impeller MaterialNoryl
Thermal ProtectionYes
Warranty3 Years
Connection Size3/4 inch
Speed Settings3
Shaft Seal MaterialCarbon/Ceramic
Ambient Temperature RangeUp to 104°F
Motor TypePermanent Split Capacitor