Instruction Sheet
“00” Cartridge Circulators
1
02-054
SUPERSEDES: May 1, 2010 EFFECTIVE: July 1, 2015
P
lant I.D. 001-934

1. Maximum operating pressure is 125 psi (862 kPa).
2. Maximum water temperature not to exceed nameplate rating.
3. Cast iron circulators are to be used for closed loop systems. Bronze or stainless steel circulators are to be used for
open loop, fresh water, or potable water systems.
4. Taco Cartridge circulator pumps are for indoor use only – employer uniquement a l´interieur.

1. Mounting position Circulator must be mounted with the motor in a horizontal position. It may be mounted
vertically with the motor up, provided that the system pressure is at least 20 psi (138 kPa).
2. Rotating body – Body has an arrow on the front that indicates direction of flow. To rotate body, remove the four body
bolts, rotate body and replace bolts. Make sure that the junction box is NOT located underneath the circulator. (The
junction box must NOT be located in the 6 o’clock position, as viewed from the motor end.)
3. Electrical connections Observe all applicable codes when connecting to power supply. The motor is impedance
protected, and does not require overload protection. Either colored wire from the capacitor box can be attached to
either colored wire from the power supply. There is no “hot” or “common” wire leading from the capacitor box. Typical
installation would be to attach the white wire to the white (common) power supply wire and either the yellow or blue
wire to the black (hot) power supply wire. The pump cannot run backwards.
             

            

               




4. Fill system with tap water The system must be filled before operating the circulator. The bearings are water lubri-
cated and should not be allowed to operate dry. Filling the system will result in immediate lubrication of the bearings.
It is always good practice to flush a new system of foreign matter before starting the circulator.
5. Circulator operation Operate the circulator for 5 minutes immediately after filling system to purge remaining air from
the bearing chamber. This is especially important when installing the circulator during the off-season.

            







Question and Answer IconNeed help?

Do you have a question about the Taco Comfort Solutions 007-F5-7IFC and is the answer not in the manual?

Taco Comfort Solutions 007-F5-7IFC Specifications

General IconGeneral
Model007-F5-7IFC
Voltage115V
Frequency60 Hz
Phase1
Motor TypePSC (Permanent Split Capacitor)
Thermal ProtectionYes

Summary

Product Application and Usage

Application Specifications

Details maximum operating pressure, temperature limits, and material compatibility for system types.

Indoor Use Restriction

Specifies that Taco Cartridge circulator pumps are intended for indoor use only.

Installation Procedures

Mounting and Body Orientation

Guidance on mounting position, rotating the body, and junction box placement.

Electrical Connection Guidelines

Instructions for electrical connections, noting impedance protection and wiring options.

System Filling and Initial Operation

Procedures for filling the system with water and initial circulator operation for air purging.

Installation Safety Precautions

Critical warnings and cautions regarding gasket use, screw replacement, electrical loads, and system pressure.

Maintenance and Replacement

Replacing Motor Assembly

Step-by-step instructions for disconnecting power, reducing pressure, and replacing the motor assembly.

Replacing Cartridge Assembly

Procedure for replacing the cartridge, including body bolts, cover plate, and product number verification.

Replacing Capacitor

Requirement to use a replacement capacitor with the same rating as the original.

Limited Warranty Statement

Warranty Coverage and Duration

Details repair or replacement for defects within three years, excluding misuse or non-compliance with instructions.

Warranty Limitations and Exclusions

Excludes consequential damages and states warranty is in lieu of all other express or implied warranties.