102
For models 095/125/155/157/175/177/195/197:
Note about built-in fan motor power supply circuit checking:
Must be done with unit power suplly switched off.
Normally fan rotates without resistance.
After having unplugged fan connector(s) from A3 board, connect a jumper on power line (blue and red wires) as shown below.
Then rotate manually the fan; if fan motor built-in power circuit is OK, a light resistance must be felt. This resistance disappears when jumper is
taken out.
Models 095 / 125 Models 155/157/175/177/195/197