Mis-setting
Maintenance
remocon
alarm
display
Alarm
contents
Judgement conditions
clearing
condition
Judgement and correction
L02
A2 and A3 boards
settings are
incompatible
A2 board judged
incompatible
with A3 board
(wrong spare part or
wrong parameters setting)
Power reset
recovery
1. Check setting parameters in the EEPROM of A2
2. Check A2 board
3. Check setting parameters in the EEPROM of A3
L08
Settings failure
Incorrect address in
EEPROM of A2 board.
Power reset
recovery
Check address setting in the EEPROM of A2
board
L09
Settings failure
Incorrect capacity in
EEPROM of A2 board.
Power reset
recovery
Check capacity setting in the EEPROM of A2
board
L10
Settings failure
Capacity not set in
EEPROM of A3 board
Power reset
recovery
Check capacity setting in the EEPROM of A3
board
L13
Settings failure
A3 and A2 board types of
unit judged incompatible
(wrong spare part or
wrong parameters setting)
Automatic
recovery
1. Check setting parameters in the EEPROM of A2
2. Check A2 board
3. Check setting parameters in the EEPROM of A3
4. Check A3 board