EasyManua.ls Logo

Technibel SCDF137C5TAA - 10. TROUBLESHOOTING; Circuit Breaker Trips or Fuse Blows; Circuit Breaker Trips After Unit On

Technibel SCDF137C5TAA
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10. TROUBLESHOOTING
CHECK BEFORE AND AFTER «TROUBLESHOOTING»
(A) Check power supply wiring.
• Check the power supply wires are correctly connected.
(B) Check power supply.
• Check that voltage is in specified range (±10% of the rating).
• Check that power is being supplied.
• WARNING: If the following troubleshooting must be done with power supplied,
be careful not to touch any uninsulated live part that can cause ELECTRIC SHOCK.
A CIRCUIT BREAKER TRIPS OR FUSE BLOWS.
• When circuit breaker is set to ON, it trips in a few moments. Resetting is not possible.
• Measure insulation resistance. There is a possibility of ground fault.
If resistance value is 1 Mohm or less, insulation is defective.
B CIRCUIT BREAKER TRIPS IN SEVERAL MINUTES AFTER TURNING AIR CONDITIONER ON.
1 • There is the possibility of short circuit.
22

Related product manuals