IST-2282.EC01.01 Istruzione / User’s Manual / Manuel d’utilisation Pag. 16/17
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) ITALY Tel. +39 02 26922890 - Fax +39 02 2133734
Tabella 1 / Table 1 / Tableau 1
Sezione Cavo
schermato
Shielded Cable
Size
Section du câble
à écran
Resistenza Cavo
[Singolo Conduttore]
Cable Resistance
[Single wire]
Résistance câble
[par conducteur]
La max distanza cui può essere insta
l-
lato ogni trasmettitore dalla centralina
Tecnocontrol Modello ID250 e SE148 è:
the maximum distance to install each de-
tector from the Gas Central Unit Model
ID250 and SE148 is:
La maxi distance à laquelle peuvent être
raccordées les sondes à les centrales
ID250 et SE148 est:
La max distanza cui può essere installato ogni
trasmettitore dalla centrali Modello
CE100, CE400, CE600, CE700 (CE380UR) è:
The maximum distance to install each detector from
the Gas Central Unit Model
CE100, CE400, CE600, CE700 (CE380UR) is:
La maxi distance à laquelle peuvent être raccordées
les sondes à les centrales CE100, CE400, CE600,
CE700(CE380UR) est:
0,75
mm
2
26
Ω/
km
100 m
300 m
1
mm
2
20
Ω/
km
150 m
400 m
1,5
mm
2
14
Ω/
km
200 m
500 m
2,5
mm
2
8
Ω/
km
400 m
800 m
Tabella 2: Interferenze con altri Gas / Table 2: Typical cross Sensitivities / Tableau 2: Interférence
GAS / GAZ
Gas Utilizzato
Test Gas Used
Gaz utilisé
ppm letti come gas
Gas concentration equivalent (ppm)
ppm lu comme gaz
TS282
EA
(1)
TS282
EA
-
H
(2)
TS282
EC
-
(3)
TS282
EC
-
H
(4)
TS282
ES
(5)
TS282
EH
(
(6)
(1) (2)
Ammoniaca /
Ammonia / Ammoniac
100 ppm
100
100
- - - 0
Anidride carbonica
Carbon dioxide / Dioxyde de carbone
5000 ppm 0 - 0.4 - - - -
(5)
Biossido di zolfo
Sulphur dioxide / Dioxyde de soufre
10 ppm
- 2 < 15 0 0
10
≈ 2
Biossido di azoto / Nitrogen dioxide / dioxyde d’azote
20 ppm < 2 < 2 - ≤ ±1
≈ - 16
Cloro /
Clorine / Chlore
1 ppm 0 0 - 0 - -
Etanolo /
Ethanol / Éthanol
200 ppm 0 0.2 < 5 0 - -
Etilene /
Ethylene
/ Éthylène
100 ppm 0 0 < 80 < 50 - ≤ 0.1
Idrogeno /
Hydrogen / Hydrogène
100 ppm 0 < 0.2 < 46 < 40 - < 1
(6) Idrogeno Solforato
Hydrogen sulphide / Sulfure d'hydrogène
15 ppm
- 3÷0 ~3 0 < 0.75 0
15
(3) (4)
Monossido di carbonio
Carbon Monoxide / Monoxyde de carbone
100 ppm
0 <1
100 100
< 1 ≤ 1
Ossido di azoto /
Nitric oxide / Oxyde nitrique
35
ppm
0 0 ~ 35 < 3 0 < 0.7
Tabella 3: Interferenze con altri Gas / Table 3: Typical cross Sensitivities / Tableau 3: Interférence
GAS / GAZ
Gas Utilizzato
Test Gas Used
Gaz utilisé
ppm letti come gas
Gas concentration equivalent (ppm)
ppm lu comme gaz
TS282
EHCN
(7)
TS282
EN
(8)
TS282
EN2
(9)
TS282
EHCL
(10)
TS282
ECL
(11)
(7)
Acido cianidrico
Hydrogen cyanide / Cyanure d'hydrogène
10 ppm
10
- - 3.5 -
(10)
Acido cloridrico
Hydrogen cloride / Acide chlorhydrique
10 ppm -
- -
10
-
Ammoniaca /
Ammonia / Ammoniac
100 ppm - - 0 0 0
Acetato di etile /
Ethyl acetate / Acétate d'éthyle
100 ppm - - < 0.5 - -
Biossido di zolfo /
Sulphur di
oxide / Dioxyde de
soufre
20 ppm 40 ÷ 75 0 - 0.4 8 < 2
(9)
Biossido di azoto
Nitrogen dioxide / dioxyde d’azote
5 ppm
- 20 ÷ -10
< 1.5
5
< ± 0.2
5
(11) Cloro / Clorine / Chlore
5 ppm
- - ≈ 10 < ± 0.2
Etanolo /
Ethanol / Éthanol
100 ppm - - 0 - < 1
Etilene /
Ethylene / Éthylène
100 ppm < 25 - 0 - < 1
Idrogeno /
Hydrogen / Hydrogène
1000 ppm - - 0 0 < 1
(6) Idrogeno Solforato
Hydrogen sulphide / Sulfure d'hydrogène
15 ppm
~ 90 ≈ 1.5 - 19 45 < -15
Monossido di carbonio
Carbon Monoxide / Monoxyde de carbone
300 ppm < 15 0 0 0 < 2
(8) Ossido di azoto /
Nitric oxide / Oxyde nitrique
35 ppm
-28 ÷ 0
35
0 0 < 1
Toluene /
Toluene / Toluène
50 ppm - - < 1.5 - -
Tabella 4 / Table 4 / Tableau 4
“S1
-
SET”(Dip
-
Switch)
Led Allarme
Alarm Led / Led d'alarme
4
ON
ON
ON
ON
OFF
ON
OF
F
OFF
OFF
ON
Il Dip-Switch va posizionato prima d’alimentare l’apparecchio.
Dip-Switch should be set with instrument powered off.
Les Dip-Switch doivent être paramétrés avant d'alimenter le détecteur