Instructions for initial setup and connection of the GSM system.
Connect the GSM modem via a 9-pole serial cable (male-female).
Connect the antenna to the GSM modem for optimal signal reception.
Connect the 8-32Vdc power supply cord to the GSM modem unit.
Configure SIM card settings, including PIN disabling, for modem operation.
Understanding LED indicators for GSM modem status and operation.
Configure serial port parameters for GSM communication.
Configure mobile phone numbers for SMS alerts and commands.
Utilize SMS commands for system control, status monitoring, and operations.
The TECNOELETTRA GSM modem, as detailed in its instruction manual, is a crucial component designed to facilitate communication and control for a TE809 GSM system. This manual, GSM-TE809-EN_rev2.doc, provides comprehensive guidance for installation, connection, operation, and maintenance, emphasizing the importance of adhering to the outlined rules for efficient and durable performance. The manufacturer, TECNOELETTRA S.r.l., reserves the right to modify the equipment without prior notice, and the manual itself is proprietary material, not to be reproduced or disclosed without authorization.
The GSM modem serves as a communication interface for the TE809 controller, enabling remote monitoring and control through SMS commands. Its primary function is to allow users to interact with the TE809 system, receive status updates, and issue operational commands via text messages from a mobile phone. This capability is particularly useful for managing generators or other connected equipment remotely, providing flexibility and convenience. The modem supports both manual and automatic modes of operation for the TE809, allowing for versatile control based on user needs. It can report various system parameters, including voltages, frequency, battery status, work hours, and fuel levels, making it a comprehensive remote diagnostic tool.
The manual highlights several key technical specifications and requirements for the GSM modem:
The GSM modem offers a range of usage features centered around SMS communication:
SETx:+[phonenumber], where x is the position (1-5) and [phonenumber] is the full international number. The system confirms successful configuration with a reply SMS.SETx command for the desired position. Numbers can be permanently deleted by sending an "empty number" command, such as SETx:.Man: Selects manual mode on the TE809.Aut: Selects automatic mode on the TE809.Test: Puts the TE809 into test mode.Off: Selects Off mode on the TE809.Reset: Resets alarms on the TE809.Start: Starts the generator in manual mode.Stop: Stops the generator in manual mode.Info: Requests an SMS with important system information and measurements.Kr: Closes the mains contactor.Kg: Closes the generator contactor.Lock: Addresses a "system block" alarm, allowing the engine to start again.Man;Start;Info), allowing for complex sequences of operations and immediate feedback.Info command): This command provides detailed status updates, including:
MODE: Current operating mode (Manual, Auto, Reset/Off).VM: Mains voltages (for TE809A and TE809Ats models).VG: Generator voltages.FG: Generator frequency.Vb: Battery voltage.H: Work hours.KG: Generator contactor status (open/closed, for TE809A and TE809Ats).En: Motor state (stopped/started).KR: Mains contactor status (open/closed, for TE809A and TE809Ats).Fuel: Fuel percentage in the tank (for TE809A and TE809G).kW: Active power.
An example message shows the format of the returned data: VGen:400; 403; 400; FG:50; Vbat:12,3; h:100; Eng:1; Fuel%:100; KG:1; kW:23;.The manual implicitly covers several maintenance-related aspects:
Overall, the TECNOELETTRA GSM modem is presented as a robust and user-friendly device designed to extend the control and monitoring capabilities of the TE809 system through convenient SMS-based communication. Its clear installation guidelines, diagnostic features, and comprehensive command set make it an effective tool for remote management.