Snow Melting
Replaces: 04/12
Snow Detector & Melting Control 665
Installation & Operation Manual
The Snow Detector & Melting Control 665 is a microprocessor-based control which operates a single zone snow melting system.
The control can operate automatically when a Snow / Ice Sensor 090 is installed or the user can manually enable and/or disable the
system. When the control is in the melting mode, the slab is maintained at a “Melting” temperature through an on/off output which
operates a contactor for electrical cables, a boiler, an injection pump or an injection valve. When the control is not in the melting mode,
the melt system can either be shut down or it can be maintained at an idle temperature for faster response and improved safety. The
665 control includes a large Liquid Crystal Display (LCD) in order to view system status and operating information.
Additional features include:
1
Red
2
Blk
3
Blu
4
Yel
5
Brn/
Slab
6
Out
7
Com
8
tN2
9
Melt/Idle
Demand
10 11
Heat
12 13
Melting
14 15 17
Sys
P1
16
Power
L
N
Test
Snow Detector & Melting Control 665
Pulse Width Modulation
Idle Demand
Melt Demand
not testing
testing
testing paused
For maximum heat,
press and hold Test
button for 3 seconds.
off
red
red
Do not apply power
Input
Snow/Ice Sensor
090 installed with
Sensor Socket
091 Optional
Input
Slab Sensor
Optional
Input
Remote Display Module (RDM)
or
Remote Start / Stop Module
or
Input
Outdoor
Sensor
Included
Input
Melt/Idle
Demand
Output
System
Pump
Input
115 V (ac)
Power
Supply
OR
Melt Demand
Idle Demand
WWSD
Water
Melting
Start
Menu Item
Stop
Do not apply power
Output
Boiler
Output
Turn on injection
pump
Output
Turn on relay for
electric cables
Output
Melt Relay
OR
OR
Signal wiring must be rated at least 300 V.
900-03
Designed and assembled in Canada by
tekmar Control Systems Ltd.
Power 115 V ± 10% 50/60 Hz 600 VA
Relays 230 V (ac) 5 A 1/3 hp
Demand 20 to 260 V (ac) 2 VA
Meets Class B:
Canadian ICES
FCC Part 15
H2028D
Date Code
• Slab Outdoor Reset
• Automatic snow detection and melt control (with 090 sensor)
• Temporary Idle
• Manual Override
• Warm Weather Shut Down
• Cold Weather Cut Out
• Remote display and adjustment capabilities
• Test sequence to ensure proper component operation
• Equipment Exercising
• CSA C US certified (approved to applicable UL standards)