TEKTINO RCC-9A maintenance manual V2.0
i
INDEX
1.Equipment description.....................................................................................................................................................1
Part description...........................................................................................................................................................1
Component layout on manifold..................................................................................................................................2
Pipeline diagram.........................................................................................................................................................3
PCA............................................................................................................................................................................ 4
2.Routine maintenance....................................................................................................................................................... 5
Maintenance of vacuum pump................................................................................................................................... 5
Change drier filter, evacuate drier filter and reset service interval time....................................................................7
Leak test......................................................................................................................................................................8
3.Troubleshooting...............................................................................................................................................................9

Questions and Answers

  • R
    Robert Perkins MDAug 15, 2025
    What to do if my Tektino Service Equipment shows high pressure alarm 004?
    • J
      jasoncruzAug 16, 2025
      If your Tektino Service Equipment displays alarm 004, but the gas cylinder gauge doesn't indicate excessive pressure, the issue might stem from a disconnected high-pressure switch plug from the PCA socket. Ensure the high-pressure switch plug is securely fastened. Another potential cause is a blockage in the pipeline connecting the compressor exit. In this case, replace the compressor exit side hoses.
  • J
    Julie TaylorAug 18, 2025
    Why is my Tektino Service Equipment not charging properly?
    • A
      Anthony HowardAug 18, 2025
      If your Tektino Service Equipment isn't charging or is charging very slowly, there are a few potential reasons: * The equipment may not have enough refrigerant. Add refrigerant until it reaches 5kg. * The system might have pressure. Run the recovery function first to relieve the pressure. * The charge solenoid may not be working. Check solenoid No. 5.
  • G
    Garrett WalkerAug 22, 2025
    What to do if Tektino Service Equipment displays alarm 005?
    • S
      Savannah WallaceAug 22, 2025
      If your Tektino Service Equipment shows alarm 005 while the auto A/C has refrigerant, the low-pressure switch plug may be disconnected from the PCA socket. Make sure to fasten the low-pressure switch plug securely. If you're using RCC-6A, the hand valves might be closed. Open the RCC-6A HP/LP hand valves.
  • D
    dfrazierAug 25, 2025
    Why does recovery not stop on my Tektino Service Equipment?
    • R
      rbarberAug 25, 2025
      If the recovery process on your Tektino Service Equipment doesn't stop, it could be due to a leakage in the automotive A/C or the equipment pipeline. Perform a leakage test, referring to the service manual for machine leakage test procedures. Another reason could be a malfunctioning compressor, which would require replacement. Note that longer recovery times are normal in winter.
  • S
    Sean GarciaAug 27, 2025
    What causes no change in recovery volume in Tektino Service Equipment?
    • C
      Caitlin HesterAug 27, 2025
      If there's no change in the recovery volume on your Tektino Service Equipment, several factors could be at play: * There might be no refrigerant in the A/C. Stop the recovery process. * The support screw of the gas cylinder load cell might not be loosened. Unscrew the support screw at the bottom of the weight sensor. * The gas cylinder load cell may not be working, or there could be a PCA failure. Calibrate the gas cylinder load cell, replace the load cell, or replace the PCA. * If you are using RCC-6A, the hand valves may not be open. Open the RCC-6A HP/LP hand valves.
  • M
    Mark VanceAug 30, 2025
    How to fix no display on Tektino Service Equipment?
    • J
      John TurnerAug 30, 2025
      If your Tektino Service Equipment has no display, the possible causes are: 1. A blown fuse (either in the power cable connection box or on the PCA). Replace the fuses. 2. A burnt PCA. Replace the PCA. 3. A loose power cable. Ensure the power cable is securely connected. 4. A malfunctioning LCD. Replace the LCD.
  • M
    Mark FrostSep 2, 2025
    Why is my Tektino Service Equipment vacuum pump injecting oil?
    • A
      ashleystoneSep 2, 2025
      If your Tektino Service Equipment's vacuum pump is injecting oil, it could be due to: * Excessive oil volume. Discharge oil to the central line. * Entrance pressure being too high. Run the Recovery function first.
  • S
    Sara JohnsonSep 5, 2025
    How to troubleshoot low vacuum degree in Tektino Service Equipment?
    • K
      Katelyn EspinozaSep 5, 2025
      If the vacuum degree is low in your Tektino Service Equipment, consider the following: 1. Insufficient vacuum pump oil. Add oil to the central line. 2. Pump oil emulsion or dirty oil. Replace the oil with new oil. 3. Plugged pump oil inlet. Clean the oil inlet. 4. Leakage in the pump connection. Check the connection. 5. Worn-out components. Replace the pump.
  • C
    Caleb CarrollSep 8, 2025
    What causes vacuum pump to be pressurized during Tektino Service Equipment recovery?
    • R
      rmartinSep 8, 2025
      If, during recovery, the vacuum pump of your Tektino Service Equipment is pressurized and there's too much oil in it after a period, it's likely that the contact between solenoid valve No. 4 and the valve base isn't well sealed. Remove solenoid No. 4 from the valve base and clean both the solenoid valve and the valve base.
  • R
    Robin HodgesSep 12, 2025
    Why is there suction in the old oil bottle during vacuum in Tektino Service Equipment?
    • C
      Cheryl NicholsonSep 12, 2025
      If, during vacuum operation, there is suction in the old oil bottle of your Tektino Service Equipment, it indicates that the contact between solenoid valve No. 2 and the valve base is not well sealed. The solution is to remove solenoid No. 2 from the valve base and clean both the solenoid valve and the valve base.

Summary

Equipment Description

Part Description

Details the various components of the equipment, including their names and functions.

Component Layout on Manifold

Illustrates the physical arrangement of components on the manifold assemblies.

Pipeline Diagram

Provides a schematic representation of the system's fluid and gas pathways.

PCA (Printed Circuit Assembly)

Details the Printed Circuit Assembly (PCA) and its connection points.

Routine Maintenance Procedures

Vacuum Pump Maintenance

Instructions for maintaining the vacuum pump, including oil level checks and changes.

Drier Filter Replacement and Service Interval Reset

Procedure for replacing the drier filter, evacuating, and resetting the service interval.

Leak Test Procedures

Methods and steps for performing leakage tests on the equipment's pipelines.