EasyManuals Logo

Telaire Ventostat 8000 Series Quick Start Guide

Default Icon
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
clear
mode
enter clear
mode
enter
Installing the Sensor
Basic Installation of the Mounting Plate and Sensor
1.
2-3.
4. 5. 6.
1. Prepare for installation by using the mounting holes configured for US or
European junction boxes.
2. Use the mounting plate as a template to mark mounting holes.
3. Secure the Mounting Plate to the wall or junction box and make necessary
wire connections.
4. Mount the Controller on the base by aligning the top clips and then securing
to the bottom clips. A “snap” sound will indicate that the sensor is secure.
The sensor will now have power. A 2 minute warm-up will take place. After 2
minutes, the sensor will stabilize and display the “Normal Mode” (current
CO2 readings).
5. At this point one of nine preset programs or one custom channel can be
selected for operation. Refer to “8. Configuring the Sensor.”
6. Finish installation by sliding the cover over the menu keys and secure with
the supplied screw.
Sensor Settings
Sensors with display can be adjusted via keypad and display or the UIP
Software program (model 2072). Sensor without display will need the program
to make any adjustments.
Altitude:
All Telaire 8000 series products are calibrated at sea level. As altitude
increases, the density of the air around us slightly decreases. This natural
phenomenon affects the accuracy of all gas sensors and introduces an error
of approximately -3% of the reading per 1,000 ft of elevation. Much of the
urbanized world is at an elevation of less than 1000 ft meaning that altitude
has very little effect on the reading and no adjustment is necessary. However,
users in locations significantly higher than sea level such as Denver, Colorado
may want to consider adjusting for elevation based on altitude to have the most
accurate reading. The altitude setting can be adjusted on the unit in 500 ft
increments.
ABC Logic™ Self Calibration System:
All Telaire 8000 series sensors are factory set with the ABC Logic™ (ABC =
Automatic Background Calibration) (formerly called TEMA) Self Calibration
feature ON. This feature allows the sensor to continually recalibrate itself
when the indoor concentrations drop to outside levels while the building is
unoccupied. Generally a building must be regularly unoccupied (with the
exception of cleaning or maintenance staff) for 4 hours or more for this self-
calibration system to operate properly. Under these conditions, ABC Logic™
should maintain sensor calibration over the lifetime of the sensor. The ABC
Logic™ should be turned OFF where a building is continuously occupied 24
hours per day, or where there could be significant sources of non-occupant
related CO2 such as greenhouses, breweries and other industrial and food
processing applications.
Standard Sensor Settings Available Via the Keypad (Display Units
Only) or PC Based UIP Interface (All Units).
Type of
Equipment
Interface w/Standard
Building Control System
Interface w/Standard
Building Control System
Interface w/Standard
Building Control System
Economizer (Hvac)
Economizer (Hvac)
Economizer (Hvac)
Economizer (Hvac)
Health & Safety
Parking/Air Intakes/
Loading Docks
Type
of
Output
Proportional
Proportional
Exponential
Proportional
Proportional
Exponential
Exponential
Proportional
Proportional
Ventilation
Rate
(cfm/
Person
Any
Any
Any
15
20
15
20
NA
NA
Analog
Output
0-10V
4-20mA
2-10V,
7-20 mA
0-10V
4-20mA
0-10V
4-20mA
0-10V
4-20mA
0-10V
4-20mA
0-10V
4-20mA
0-10V
4-20mA
0-10V
4-20mA
CO
2
Control
Range
(ppm)
0-2000
0-2000
0-2000
0-1100
0-900
0-1100
0-900
0-9999
0-2000
Optional
Relay
Setpoint
(ppm)
1000
1000
1100
1100
900
1100
900
5000
700
Relay
Hysteresis
(ppm)
50
50
50
50
50
50
50
500
50
Setting
No
1
2
3
4
5
6
7
8
9
Sensor Setting
The standard factory settings are the typical settings used when a CO
2
sensor is connected to a building control system. If the installation is
somewhat unique or specialized, the user can customize certain characteris-
tics of the sensor. For example, non-factory settings may be applicable when
the sensor is being connected to equipment that has a fixed input range (e.g
actuators used with economizer systems).
Outlined below are the adjustable parameters of the sensor and the factory
setting. In addition to these adjustable features, the programming interface
allows for a fast and simple adjustment of sensor calibration.
8000 Series Adjustment Parameters and Factory Settings
Range
0-10,000 Ft
On/Off
1 to 9
0-10,000
4-20mA / 0-10V
Select One
0-10,000 PPM
0-10,000 PPM
Factory Setting
0 Ft
On
1
0-2,000
4-20mA / 0-10V
Proportional
1000 PPM
50 PPM
Adjustment
Altitude Above Sea Level
ABC Logic™
Select Standard Setting
Customize Setting
PPM Range
Output Range
Proportional/
Exponential Output
Relay Setpoint
Relay Hysteresis
Standard Pre-Programmed Settings:
There are 9 Standard settings that can easily be selected using the keypad
(display units only) or the PC based UIP Program. The chart below describes
each of the settings. The definitions for some of the terms used in the chart
are described in more detail as part of the custom settings section to follow.
Settings 1, 2 and 3 are applicable for automated or computerized building
control systems.
Settings 4 to 7 are specifically designed for operation with economizer controls
and actuators where a 0-10 VDC signal will provide 0-100% outside air modula-
tion. These control settings provide different modulation ranges depending on the
target cfm-per-person ventilation rate desired. As described below the exponential
setting is best used in applications that have large volumes of air and people
such as auditoriums, gyms and large conference areas.
Setting 8 is intended for use in applications related to occupational health and
safety where users may want to measure concentrations in relation to the
5000 ppm 8 hour exposure levels established by OSHA (Occupation Safety
and Health Administration).
Setting 9 is intended for use in parking garages where CO2 can be used as an
indicator of the presence of combustion fumes. As part of most types of
combustion, CO2 is generated at a rate that is 50 times or more of other more
harmful contaminants. This is particularly the case with the extensive use of
catalytic converters that tend to remove most of the carbon monoxide from
vehicle exhaust. The 700 ppm setting should maintain levels of other exhaust
contaminants well below levels of concern.
Custom Settings:
In addition to the 9 standard settings programmed into the 8000 series, users
can also custom program the sensor for their own application. Outlined below
is a brief description of each of the adjustable custom settings:
62332-007 09/08/2004

Other manuals for Telaire Ventostat 8000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Telaire Ventostat 8000 Series and is the answer not in the manual?

Telaire Ventostat 8000 Series Specifications

General IconGeneral
BrandTelaire
ModelVentostat 8000 Series
CategoryController
LanguageEnglish