Telca TAC-12D-10 - Table of Contents; Technical Data; General

Default Icon
10 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service manual: TAC-12D-10
1/9
Contents:
1. General
2. Technical data
3. Assembly
4. Electrical connection
5. Commencing operation and control behavior
6. Maintenance
1. General
The cooling circuit is designed in the form of a maintenance-free, hermetically sealed
system. The cooling unit is filled with the required quantity of refrigerant at the factory,
checked for leaks, and subjected to a functional test run. The installed maintenance-free
fans are mounted on ball bearings, protected against moisture and dust, and fitted with a
temperature monitor. The life expectancy is at least 30,000 operating hours. The cooling
unit is thus largely maintenance-free. All that may be required from time to time is to
clean the components of the external air circuit using a vacuum cleaner or compressed
air if they become visibly dirty.
Maintenance interval: 12 months. Depending on the level of contamination in the
ambient air, the maintenance interval may be reduced to suit the air pollution intensity.
2. Technical data
Model No. TAC-12D-10
Dimensions WxHxD 420 x 1000 x 180 mm
Cooling output @L35/L35
1200 W
Heating output 1000 W
Rated voltage Volt/Hz 220VAC, 50/60Hz
Rated current 3.3 A (Cooling)
4.5 A (Heating)
Temperature range -40°C ~ +55°C
Power consumption 720 W (Cooling)
1000 W (Heating)
Air circuit (External) 570 m
3
/h
Air circuit (Internal) 450 m
3
/h
Noise 62dB
Refrigerant R134a
Protection category IP55
Weight 34Kg
Special voltages available on request.