Hi = High Heat Limit = This is the highest allowed heating setpoint. The
user will not be allowed to set a setpoint temperature higher than
this value.
Lo = Low Cool Limit = This is the lowest allowed cooling setpoint. The user
will not be allowed to set a setpoint temperature lower than this
value.
FL = Timer to remind the home owner to maintain the filter. Default setting
is off. The timer runs when the system is on and can be set at 0 (OFF)
or 1000 hours. When the time expires FL is displayed. Press any
button to reset and return to the normal display.
CY = Cycle Timer allows a compressor to rest between cycles. Can be set
from 0 to 5 minutes in 1 min increments.
WARNING: A wrong short cycle setting can
damage your equipment.This should only be
changed by a trained HVAC professional.
CL = Calibration offset. Changes the displayed temperature from the
actual temperature by +3 to -3 degrees in one degree increments.
Increasing the offset by +2 will cause the thermostat to display a
temperature that is 2 degrees higher than the actual room
temperature
!