Tempcool TC-120B4 - Troubleshooting Common Issues; Cooling and Airflow Problems

Default Icon
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7|Page
Condenserfanruns,
compressordoesnot
Faultycompressorwiring
orbadcompressor
Checkwiring.Replacecompressorifnecessary.
Compressorrunsbut
condenserfandoes
not
Faultycondensermotor
wiring
Checkwiring.
Motoroffonthermal
overload
Allowmotortocoolandseeifmotorrestarts.Check
ampdraw.Iftoohighopendriversheave.Replace
motorifthermaloverloadcontinuestotrip.
Faultymotor Replacecondenserfanmotor
Problem Cause Remedy

LowAirflow Dirtyfilterorcoil Replacefiltersandcleancoils
RestrictiveAccessoriesor
Ductwork
Removeorreducerestrictions.Straightenductwork,
reducelengthorincreaseductsize.Cleardebrisoutof
inlets,outletsandducts.Moveunitawayfromwallsor
otherrestrictionstoairflow.
Drivensheavetoofar
open
Closesheavetoincreaseblowerspeed.
Vbeltsslipping Cleanorreplacebeltsandtighten.
Insufficientcooling Incorrectlysizedunit Checksystemrequirements.
LowAirflow SeeLowAirflowProblem
LowRefrigerantLevels Checkrefrigerantpressuresandcharge
Defectiveorobstructed
TXvalve
Repairorreplacevalve
Temperaturesignalto
CopelandCompressor
controllernotcorrect
SignalfromWatlowcontrollertoCoplandshouldbe+5.0
vdcformaximumoutputfromthecompressor.The
voltagewilldropifthecoiltemperaturedropscloseto
32
o
F.ChecksensorWatlowforproperoperation
Compressorunloader
solenoidisstuckopen
SeeCoplandtroubleshootinginformation.Replacevalve
ifnecessary