Symbol Name
Description
#1: Factory set value
#1
The following parameter symbols are displayed one by one every time the SET key is pressed.
InPt Setting
-50 to1350 C
K
-50 to1000 C
J
-50 to 1750 C
S
-20 to1300 C
N
-20 to400 C
T
E
-50 to1000 C
**A: INPUT TYPE SYMBOL TABLE
Input type
Range
Main input type select
(InPt)
Input type selection as:thermocouple(TC),RTD,etc.
See **A "INPUT TYPE SYMBOL TABLE"
K
Alarm type selection
(ALd)
Select the type of alarm1 and alarm 2
range:0~3 See **B "ALARM TYPE TABLE"
3
Low setting limiter
(LSPL)
Lowest value of PV display
(PAL)
Highest value of PV display
(PAH)
Set lower point within input
see 14. chapter "INPUT RANGE TABLE"
0
Up setting limiter
(USPL)
Set higher point within input
see 14. chapter "INPUT RANGE TABLE"
400
10
Proportional reset
(rE)
Overshooting restricted by the proportional effect.
2
3
0
5000
0
0
100
PV follow-up
(SOFT)
PV variable-value control, Setting range: 0 to 10
PV will response slower if SOFT is bigger.
Output forced turning off when the PV value overshooting .
Setting range: 0 to 100
Lowest value display when analog signal inputs,Such as 4-20mA input.
Highest value display when analog signal inputs,Such as 4-20mA input.
The value of PV display when input 4 mA. tandard analog signal input. Only for s
The value of PV display when input 20 mA. tandard analog signal input. Only for s
Overshooting turn off
(OFF)
Only for standard analog signal input (current or voltage inputs) .
Range:0~3
Decimal point
(dP)
Output manipulated variable
lowest limit (OTL)
Output manipulated variable
highest limit (OTH)
Output manipulated variable lowest limit .
Or low limit output calibration whenthe output is continuous current or
voltage,such as 4-20 mA output. Range : 0 to 100%
Output manipulated variable highest limit .
Or high limit output calibration whenthe output is continuous current or
voltage,such as 4-20 mA output. Range : 0 to 100%
50 to1800 C
B
R
-20 to1750 C
W5Re/W26Re
0 to2300 C
InPt
-1999 to 9999 -1999 to 9999
0-5VDC 0-10VDC
*
*
*
*
-199 9to 9999 -199 9to 9999
1-5VDC 2-10VDC
-1999 to 9999
DC0-20mA
-1999 to 9999
DC4-20mA
-199.9 to600.0 C
-50.0 to150.0 C
Pt100
Cu50
1 All input change in the above groups is possible by keyboard,
except for 0 to 10VDC and 2 to 10VDC.
2 If you need the 0 to 10VDC & 2-10VDC input type, please explain
when ordering.
Because the hardware
of these 2 inputs are different.
*
After the value be registered ,when no parameter setting is required, after the value be registered ,Press the SET key for 3 s to return the
instrument to the normal display.
PVvalue
PVvalue
PVvalue
PVvalue
PVvalue
PVvalue
PVvalue
PVvalue
PVvalue
PVvalue
PVvalue
PVvalue
ALd=0
AL1 alarm mode (High alarm) AL2 alarm mode (Low alarm)
HIGH
HIGH
HIGH
HIGH
HIGH
HIGH
HIGH
HIGH
HIGH
HIGH
HIGH
HIGH
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
AL1
AL1
AL2
AL2
SV+AL1
SV+AL1
SV+AL1
SV+AL1
AL1 0
AL1 0
AL2 0
AL2 0
AL1<0
AL1<0
ALd=1
SV-AL2
SV-AL2
SV-AL2
SV-AL2
AL2<0
AL2<0
ALd=2
ALd=3
HYS
HYS
HYS
HYS
HYS
HYS
HYS
HYS
HYS
HYS
HYS
HYS
**B: ALARM TYPE TABLE
Alarm code
Alarm specification
:SV :Alarm set value
ALd set value
SV
SV
SV
SV
SV
SV
SV
SV
AL1:Process alarm
AL1:Process alarm
AL2:Process alarm
AL1:Deviation alarm
AL1:Deviation alarm
AL2:Deviation alarm
AL2:Deviation alarm
AL2:Process alarm
AL1 Process high alarm
AL1 Process high alarm
AL2 Process low alarm
AL2 Process low alarm
Alarm1 ON
Alarm1 ON
Alarm1 ON
Alarm1 ON
Alarm1 ON
Alarm1 ON
Alarm2 ON
Alarm2 ON
AL1 Deviation high alarm
AL1 Deviation high alarm
AL2 Deviation low alarm
AL2 Deviation low alarm
AL2 Deviation low alarm
AL2 Deviation low alarm
AL1 Deviation high alarm
AL1 Deviation high alarm
NOTE:
Alarm differential
gap=HYS,when
P 0(PID action)
TS80B-E1
5