8
IS GATEWAY INSTALLED AS SERVICE EQUIPMENT?
NO
GATEWAY IS NOT INSTALLED AS SERVICE EQUIPMENT
REMOVE NEUTRAL-GROUND BONDING STRAP
YES
GATEWAY IS INSTALLED AS SERVICE EQUIPMENT
INSTALL MAIN BREAKER
See Wiring Reference in the Installation Reference Manual for breaker types
MAKE BACKUP GATEWAY AC POWER CONNECTIONS
9
SUPPLY SIDE CONDUCTORS
1 ¼”
¾”
275 in-lbs
120 in-lbs
5/16”
3/16”
6 AWG - 250 kcmil
6 AWG - 250 kcmil
6 AWG - 250 kcmil
14 AWG - 2/0