1
LUXA 103-100 DE WH
1030012
LUXA 103-101 DE WH
1030013
307343
Motion detector
EN
1. Basic safety information
Danger of death through electric shock or fire!
Installation should only be carried out by a
qualied electrician!
WARNING
•
The device conforms with EN 60669-2-1 if installed
correctly
2. Proper use
•
Motion detector for automatic lighting control dependent
on presence and brightness; LUXA 103-101 DE: suitable
for automatic lighting and HVAC control
•
Suitable for ceiling installation (false ceilings) indoors
•
Suitable for toilets, small rooms, workplaces, ofces, etc.
Disposal
Dispose of the device in an environmentally sound manner
(electronic waste)
3. Device description
Sensor unit
Power supply unit
3 potentiometers for setting
time delay (TIME), bright-
ness value (LUX) and detec-
tion area (metres);
additional setting of HVAC
time (TIME 2) in the case of
LUXA 103-101 DE
red LED
4. Installation and connection
!
Secure device with an upstream type C circuit breaker
(EN 60898-1) with a maximum of 10 A.
!
Secure device with an upstream type C circuit breaker
(EN 60898-1) with a maximum of 6 A (HVAC channel 2).
Installing the motion detector
L Installation height: 2 – 3 m
L Cable length: 100 cm
L Motion detector requires clear line of sight to people
Disconnect power source
0FF
230V
Create a ceiling opening of Ø 65 mm
=65
Ø
6 - 8 m m
5 0 - 6 0 m m
Screw open and ip open the power supply unit
Connect power supply unit and sensor unit according to the
wiring diagram
L Recesses in the power supply unit can be adjusted to the
cable diameter (min. Ø 3 - max. Ø 12.5 mm)
Ø 3 - Ø 6 mm
Max. Ø 12.5 mm
!
ATTENTION: the network connector must be rmly in place
Push the power supply unit through the ceiling opening
and attach the sensor with tensioned springs in the ceiling
Ø = 65
Connect motion detector to power supply