G. SETPOINTS MENU
EVCA Modulating Fire Test Procedures and Specifications
APPENDIX D (Cont) - TSBC
TM
SETPOINTS Menu
Display
Factory
Settings
Range/Choices Description
Operational
SP
180 60 to 230 F
Setpoint used in Local Setpoint Mode when not servicing a Domestic Hot Water
Priority (DHWP) request.
On Point -5 0 to 99 F
The boiler starts when the water temperature drops ‘On Point’ degrees below the
setpoint.
Off Point 15 0 to 99 F
The boiler stops when the water temperature rises ‘Off Point’ degrees above the
setpoint.
High Temp
Stop
Boilers
230
60 to 230 F
The boiler stops when water temperature is above the High Temperature Stop
setpoint. This setpoint is active in every control mode.
DHWP
Setpoint
180
140 to 230 F
The Domestic Hot Water Priority (DHWP) Setpoint is active when DHW Input
(DP) closes and “DHWP” parameter is set to “yes” and Local SP Mode is
selected. When the contact is closed, the boiler outlet is maintained at, or above,
the DHW Setpoint.
Only visible when DHWP equals Yes.
WWSD
Setpoint
70 40 to 90 F
The Warm Weather Shutdown (WWSD) Setpoint used to disable boiler and or
system pump operation when enabled by setting the “WWSD” parameter to
“WWSD of Boiler”, “WWSD of Sys Pump” or “Both”.
Only visible when WWSD does not equal Off.
Max SP
Boilers
230
140 to 230 F The Maximum Operational Setpoint for all possible Local and Remote modes.
Min SP 70 60 to 230 F
The Minimum Operational Setpoint is the lower limit for all Local and Remote
modes.
Min BIT 120 60 to 235 F Low Boiler Inlet Temperature alarm and event setpoint.
Min In H2O
Temp
130 110 to 180 F
Minimum Inlet Water Temperature setpoint used as the Mixing Valve inlet
temperature setpoint.
Only visible when Mixing Valve equals Yes.
Max H2O
Delta T
50 20 to 50 F
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature
setpoint used as the Mixing Valve differential temperature setpoint.
Only visible when Mixing Valve equals Yes.
Max
Delta T
Hold
50 20 to 50 F
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature used
to hold modulation rate at low fire.
Page 17 of 22
Boilers
230
Water
Heaters
200
Boilers
230
Water
Heaters
200
140