I. MANUAL MODE MENU
EVCA Modulating Fire Test Procedures and Specifications
APPENDIX D (Cont) - TSBC
TM
MANUAL MODE Menu
Display
Factory
Settings
Range/Choices Description
Boiler
Man/Auto
Auto
Man
Auto
Man: Remain in Manual Mode.
Auto: Return to Boiler Mode specified by parameter/boiler conditions.
Activated only when in Supervisor Mode.
Modulation
Rate
Varies 0 to 100
Sets the modulation rate to be used for boiler when in Manual Mode.
Activated only when in Supervisor Mode and Boiler Man/Auto = Man.
Boiler
On/Off
Varies
On,
Off
Sets the boiler start/stop status when in Manual Mode.
No: Turn off boiler if running, otherwise remain off.
Yes: Turn on boiler if off, otherwise remain on.
Activated only when in Supervisor Mode and Boiler Man/Auto = Man.
Mixing
Valve
M/A
Auto
Man
Auto
Man: Remain in Manual Mode.
Auto: Return to Control Mode specified by parameter/boiler conditions.
Activated only when in Supervisor Mode.
Mixing
Valve
Varies 0 to 100
Sets the Mixing Valve % Open to be used for valve when in Manual
Mode.
Activated only when in Supervisor Mode and Mixing Valve M/A equals
Man.