3= inverted PWM (0%= 100%PWM .. 100% = 0% PWM)
Configuration external input 1
0 = No function
1 = Occupancy sensor (Open = Occupied)
2 = Occupancy sensor (Closed =Occupied)
3 = Window contact (Open = Window Open)
4 = Window contact (Closed = Window Open)
5 = Disable heating (Open = Heating disabled)
6 = Disable heating (Closed = Heating Disabled)
7 = Disable cooling (Open = Disable Cooling)
8 = Disable cooling (Closed = Disable Cooling)
9 = Dew Point Sensor (Open = Dewpoint crossed, disable
cooling)
10 = Dew Point Sensor (Closed = Dewpoint crossed,
0
Configuration external input 2
0 = No function
1 = Occupancy sensor (Open = Occupied)
2= Occupancy sensor (Closed =Occupied)
3 = Window contact (Open = Window Open)
4 = Window contact (Closed = Window Open)
5 = Disable heating (Open = Heating disabled)
6 = Disable heating (Closed = Heating Disabled)
7 = Disable cooling (Open = Disable Cooling)
8 = Disable cooling (Closed = Disable Cooling)
9 = Dew Point Sensor (Open = Dewpoint crossed, disable
cooling)
10 = Dew Point Sensor (Closed = Dewpoint crossed, disable
0
Configuration Sensor Input
0= none
1 = Change Over Temp sensor (NTC10K)
2 = Ext. Temp sensor (NTC10K)
0
ESI (Energy Savings Input) - ON delay
ON delay for ESI. Delays Energy stop by n seconds
0
OCC input - OFF delay
0…65535 -> 0…65535 seconds
1800