Thermokon LCF02 5DO RS485 Modbus - HOLDING REGISTERS - GENERAL SETTINGS; Device Identification, Display, and Power; Sensor Offset, Language, Password, and Limits; Key Lock and Display Configuration

Thermokon LCF02 5DO RS485 Modbus
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Issue Date: 06.04.2021 Page 8 / 12
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Deutschland · tel: 02778/6960-0 · fax: -400 · www.thermokon.de · email@thermokon.de
LCF02-5DO_Datasheet_en.docx © 2021
Holding Register
General settings
Address
Access
Description
Resolution / Unit
Default
256
0x0100
Read-write
Customer set Device location identification
0…65535
1.0
0
257
0x0101
Read-write
LCD Temperature Unit
0=°C
1=°F
0
258
0x0102
Read-write
Beeper Intensity
0=Off
1..5 (Volume)
5
259
0x0103
Read-write
Backlight intensity operated
0..100
1.0
%
80
260
0x0104
Read-write
reserved
261
0x0105
Read-write
Backlight operating delay setting
1….255 = 1…255 seconds ON
1.0
s
15
262
0x0106
Read-write
Internal Sensor Temperature Offset
(added to meaured value)
-50…50 = -5,0..+5,0 °C
-250…250 = -25,0..+25,0 °F (257 0x0101 = 1)
0.1
°C/°F
0
263
0x0107
Read-write
external Sensor Temperature Offset
(added to meaured value)
-50..+50 = -5,0..+5,0 °C
-250…250 = -25,0..+25,0 °F (257 0x0101 = 1)
0.1
°C/°F
0
264
0x0108
Read-write
Display language
0= German
1= English
0
265
0x0109
Read-write
Individual passwords setting
001-999
default=987, 000 = no password
987
266
0x010A
Read-write
External temperature (limiter) sensor high limit
(338=3, for limiter)
-200..+1000 = -20,0…+100,0 °C
0..2100 = 0..+200 °F (257 0x0101 = 1)
0.1
°C/°F
40°C /
1100°F
267
0x010B
Read-write
External temperature (limiter) sensor low limit
(338=3, for limiter)
-200..+1000 = -20,0…+100,0 °C
0..2100 = 0..+200 °F (257 0x0101 = 1)
0.1
°C/°F
0°C /
320°F
268
0x010C
Read-write
Power failure
0=keep off after power-on-reset
1=return to last state after power failure
2=switch on after power-on-reset
1
269
0x010D
Read-write
Key-lock
0x00=unlocked
0x01=lock on/off
0x02=lock mode
0x04=lock clock
0x08=lock fan speed
0x10=lock temp setting
0x1F=lock all keystrokes
Once a locked key is pressed the LOCK symbol shall be
displayed and blink twice.
0
270
0x010E
Read-write
Display Settings
0b00000001= show Setpoint (if no setpoint is shown the
setpoint keys are locked = 0x010D = 0x10=lock temp setting)
0b00000010= show Room temperature
0b00000100 = show valve symbol
0b00001000 = show PI-Loop percentage
0bxxx10000 = show Room temperature from Register 0x205
(if only room temp or setpoint is shown, then in big numbers)
15
Set point settings
Address
Access
Description
Resolution / Unit
Default
271
0x010F
Read-write
Default Setpoint after Power On Reset
0..500 = 0…50,0 °C
300..1200 = +30,0..+120,0 °F (257 0x0101 = 1)
0.1
°C/°F
210 /
700
272
0x0110
Read-write
Setpoint temperature lower limit
0..500 = 0..50,0 °C
300..1200 = +30,0..+120,0 °F (257 0x0101 = 1)
0.1
°C/°F
160 /
600
273
0x0111
Read-write
Setpoint temperature upper limit
0..500 = 0..50,0 °C
300..1200 = +30,0..+120,0 °F (257 0x0101 = 1)
0.1
°C/°F
300 /
860
274
0x0112
Read-write
Setpoint increment/decrement value
1..100 = 0,1…10,0 °C
1..500 = 0,1..50,0 °F
0.1
°C/°F
5 /
10
275
0x0113
Read-write
ECO mode temperature setpoint cooling
250..450 = +25,0..+45,0 °C
750..1100 = +75,0..+110,0 °F
0.1
°C/°F
300 /
860
276
0x0114
Read-write
ECO mode temperature setpoint heating
120..240 = +12,0..+24,0 °C
50..750 = +5,0..+75,0 °F
0.1
°C/°F
190 /
660