CONFIGURATION OF PARAMETERS/FUNCTIONS
It is possible to enter the basic parameters using the 7 segment display and the <ENTER> and <DOWN> keys.Press
and hold <ENTER> for 5 sec to enter the conguration menu. Press <DOWN> to pass from a parameter to another,
press <ENTER> to increase the function value of the function selected. You will exit the conguration mode after 20
seconds without pressing any key.
Depending on the type of installation, the actuator is oriented di󰀨erently. The electronic board may be upside down. In
this case you can reverse the display by pressing both keys (enter-down) per one second. This will reverse the display.
ref. display parameter description
val.
*default*
value description
101
DOOR WEIGHT
Only weights that the automation can
manages safely can be enter, based
on the door dimensions parameter
setting
MANDATORY PARAMETER
0
1
*2*
3
4
5
6
7
8
9
25 KG
50 KG
75 KG
100 KG
125 KG
150 KG
175 KG
200 KG
225 KG
250 KG
102
DOOR DIMENSIONS
Only weights that the automation
can manages safely can be enter,
based on the door weight
parameter setting
MANDATORY PARAMETER
0
1
2
*3*
4
5
6
7
8
9
500 mm
600 mm
700 mm
800 mm
900 mm
1000 mm
1150 mm
1300 mm
1450 mm
1600 mm
103
ARCHITRAVE DEPTH
Denes the depth of the architrave
MANDATORY PARAMETER
0
*1*
2
3
4
5
6
7
8
9
-30 mm
0 mm
40 mm
60 mm
100 mm
140 mm
180 mm
220 mm
260 mm
300 mm
104
ACTIVATION SENSORS LOGICS
Denes the control logics of the
activation sensors
0
1
*2*
3
4
5
N.O.
N.C.
NO. with closing safety sensor that activates
and is located inside(exit only)
N.C. with closing safety sensor that activates
and is located inside(exit only)
NO. with closing safety sensor that activates
and is located outside (entrance only)
N.C. with closing safety sensor that activates and is located
outside (entrance only)
CONFIGURATION OF AUTOMATION PARAMETERS
S200
Architrave depth
closing safety sensor
inside-
inside-