instructions for installation
S200
CONFIGURATION OF AUTOMATION PARAMETERS
ref. display parameter description
val.
*default*
value description
122
DOOR OPEN PAUSE TIME.
Regulates the open door pause time after radar
reading.
0
*1*
2
3
4
5
6
7
8
9
0 s
5 s
10 s
15 s
20 s
30 s
40 s
60 s
120 s
180 s
123
DYNAMIC INCREASE OF OPENING TIME
When this parameter is enabled it automatically in-
creases the time the door remains open when a large
ow of users is detected. When the door closure is
interrupted by the safety sensor on closure or by a
radar, the open time “q” in increased by 2 seconds
at every interruption. When a complete closure takes
place, the time returns to the time “q” preset.
*0*
1
Disabled
Enabled
124
REGULATION OF SENSITIVITY TO
OBSTACLE RECOGNITION
Regulates the force applied to the obstacle in
full energy before stopping.
0
1
2
3
*4*
5
6
7
8
9
0 is the minimum force and 9 is the greatest.
125
ANTIWIND FORCE WITH CLOSED
DOOR
Force applied on closed door edge to prevent open-
ingn case of wind.
*0*
1
2
3
4
5
6
7
8
9
Disabled
Increasing the value increases the force.
126
WIND RESISTANCE FORCE WITH
OPEN DOOR
Force applied on open door edge that prevents
closure in case of wind.
*0*
1
2
3
4
5
6
7
8
9
Disabled
Increasing the value increases the force.
127
DELAY TIME FOR ELECTRI-
CLOCKS
Delay time between release of electric lock / electric
block and the beginning of door opening. Permits use
of locks requiring time to release.
*0*
1
2
3
4
5
6
7
8
9
Disabled
0,5 s
1,0 s
1,5 s
2,0 s
2,5 s
3,0 s
3,5 s
4,0 s
5,0 s
128
UNLOCK TIME
The param eter indicates the duration of the unlock-
ing pulse of the electric lock in im pulsive mode.
*0*
1
2
3
4
5
6
7
8
9
0,2 s
0,5 s
1,0 s
1,5 s
2,0 s
2,5 s
3,0 s
3,5 s
4,0 s
5,0 s