TOPVERT L1 Series
E-
18
Group 2: Digital Input/Output parameters
Parame
ters
Functions Settings
Factory
Setting
User
Pr2-00
External operation
0: 2-wire mode 1- FWD/STOP, REV/STOP
0
1: 2-wire mode 2- RUN/STOP, REV/FWD
2: 3-wire mode -RUN,STOP, FWD/REV
Pr2-01
Multi-Function Digital input
MI1
0: No definition
1
Pr2-02
Multi-Function Digital input
MI2
1: Multi-step speed command 1
2
Pr2-03
(Factory Reserved) 2: Multi-step speed command 2
3
Pr2-04
(Factory Reserved) 3: Multi-step speed command 3
4
Pr2-05
(Factory Reserved)
4: Multi-step speed command 4
5
Pr2-06
(Factory Reserved)
5: External Reset
14
6: Clear counter
7: 1st and 2nd acceleration/ deceleration time
select
8: Acceleration/deceleration inhibit
9: Force the frequency command from AI1
10: (Factory Reserved)
11: (Factory Reserved)
12: Emergency Ramp to stop
13: Disable PID function
14: External fault input (EF)
15: B.B. traces from the bottom upward
16: B.B. traces from the top downward
17: Force operation command to external
18: Cancel the auto acceleration/ deceleration
function
19: (Factory Reserved)
20: (Factory Reserved)
21: (Factory Reserved)
22: Cancel PLC Run
23: Pause PLC Run
24: Up command
25: Down command
26: Zero speed is replaced by DC braking
27: Pause
28: Disable dwell function
29: Disable traverse function
30: Disable Speed search during start-up
31: Disable EEPROM write function
32: Counter Trigger input (MI2 only)
33~41: (Factory Reserved)
42: Motor Select
43: Confirm signal of Motor selection
44: Disable reverse operation
45: Disabled forward operation
Pr2-07
UP/DOWN command mode
Bit 0
(bxxxx0)
0: Up command-Accel by the Acc. time
b00000
1: Up command-Accel by Pr2-08
setting
Bit 1
(bxxx0x)
0: Down Command-Decel by the Dec.
time
1: Down Command-Decel by Pr2-08
setting
Bit 2
(bxx0xx)
(Factory Reserved)
Bit 3
(bx0xxx)
0: FWD/REV terminals act by edge
trigger

Related product manuals